| 2020-05-19 09:28:50 | | | | | | | 1) SUBMIT THE DRAWINGS LISTED ON EXHIBIT A: SK1.0, SK | | | 2.0, AND SK2.1. THE DRAWINGS SHALL INCLUDE: | | | | | | A) THE BOILER ROOM AND NEW BOILER LOCATIONS WITH | | | REQUIRED CLEARANCES DISTANCE MEASUREMENTS FOR SERVICE | | | ACCESS AND REPLACEMENT- SECTION 306.1 FBC FG. | | | | | | B) VENTING DIAGRAMS SHOWING THE TYPE AND SIZE OF GAS | | | VENTS, GAS VENT RUNS, AND TERMINATION LOCATIONS- | | | SECTION 503 FBC FG. | | | | | | 2) EXHIBIT A INDICATES THE COST OF THE BOILERS, | | | EXPANSION TANK, AND CIRC. PUMP ARE TO BE PROVIDED BY | | | OWNER. PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR, | | | MATERIALS, APPLIANCE AND EQUIPMENT. PLEASE PROVIDE A | | | TOTAL VALUE THAT INCLUDES THE COST OF THE EQUIOMENT- | | | SECTION 109.3 WPB. | | | 3) INSULATION OF HOT WATER PIPING SHALL COMPLY WITH | | | FBC-PLUMBING SEC.607.5. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|