Plan Review Notes
Plan Review Notes For Permit 20031094
Permit Number 20031094
Review Stop M
Sequence Number 1
Notes
Date Text
2020-05-12 07:55:19PLEASE SEE 1ST REVIEWERS COMMENTS. I DO NOT SEE
 ANYTHING IN THESE SUBMITTED FILES THAT HE WAS
 REQUESTING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-03-24 11:31:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20031094
 3/24/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT THE DRAWINGS LISTED ON EXHIBIT A: SK1.0, SK
 2.0, AND SK2.1. THE DRAWINGS SHALL INCLUDE:
  
 A) THE BOILER ROOM AND NEW BOILER LOCATIONS WITH
 REQUIRED CLEARANCES DISTANCE MEASUREMENTS FOR SERVICE
 ACCESS AND REPLACEMENT- SECTION 306.1 FBC FG.
  
 B) GAS PIPING AND WATER PIPING DRAWINGS SHOWING ALL
 REQUIRED ALTERATIONS AND NEW INSULATION INSTALLATIONS.
 PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR GAS
 PIPING- SECTION 107.2.1 WPB.
  
 C) COMBUSTION AIR CALCULATIONS AND THE MEANS OF
 PROVIDING THE COMBUSTION AIR- SECTION 304 FBC FG.
  
 D) VENTING DIAGRAMS SHOWING THE TYPE AND SIZE OF GAS
 VENTS, GAS VENT RUNS, AND TERMINATION LOCATIONS-
 SECTION 503 FBC FG.
  
 2) EXHIBIT A INDICATES THE COST OF THE BOILERS,
 EXPANSION TANK, AND CIRC. PUMP ARE TO BE PROVIDED BY
 OWNER. PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR,
 MATERIALS, APPLIANCE AND EQUIPMENT. PLEASE PROVIDE A
 TOTAL VALUE THAT INCLUDES THE COST OF THE EQUIOMENT-
 SECTION 109.3 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  