| 2020-06-26 15:33:31 | PLAN REVIEW - NFIP |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW - FINISHED CONSTRUCTION ELEVATION |
| | CERTIFICATE |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. FEMA FORM 086-0-33 ELEVATION CERTIFICATE IS OUT OF |
| | DATE. SUBMIT ELEVATION CERTIFICATE ON CURRENT FORM. |
| | |
| | 2. STATE NUMBER OF FLOOD OPENINGS ON LINE A9 (B). |
| | |
| | 3. STATE NET AREA OF FLOOD OPENINGS ON LINE A9 (C). |
| | |
| | 4. LINE C2 (E) SHOWS ELEVATION OF EQUIPMENT SERVICING |
| | THE BUILDING AT 6.92. THIS ELEVATION SHALL BE AT OR |
| | ABOVE DESIGN FLOOD ELEVATION OF 8.0 FT. NAVD88. |
| | |
| | 5. PHOTOGRAPHS PROVIDE DO NOT COMPLY WITH THE |
| | REQUIREMENTS OF LINE A6. PROVIDE PHOTOS OF FLOOD VENTS. |
| | |
| | 6. PROVIDE PRODUCT APPROVALS FOR FLOOD VENTS - SMART |
| | VENT MODEL 1540-520. |
| | |
| | 7. LOCATION OF FLOOD VENTS ARE MISSING ON PLANS. SUBMIT |
| | A REVISION TO PERMIT 18050588. SHOW LOCATION OF FLOOD |
| | VENTS ON FOUNDATION PLAN. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |