2020-04-28 15:15:26ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SUBMIT A PANEL SCHEDULE
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
  
 2) RISER DIAGRAM AND LOCATION OF PANEL
  
 SHOW LOCATION OF SERVICE AND PANELS NO LOCATION SHOWN.
 E3601.6.2 SERVICE DISCONNECT LOCATION.
  
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5;
 FBC 107.2.1
  
  