| Date |
Text |
| 2020-03-24 16:07:42 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20031062 |
| | ADD: 1900 CONSULATE PL. SUITE: 1003 |
| | CONT: ZQUEST RESTORATION |
| | TEL: 954-563-9606 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY MARCH 24TH/ 2020 |
| | ACTION: DENIED |
| | |
| | IS THE UNIT # 1003 ON THE 1ST FLOOR. |
| | 1) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2017) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| | SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS: |
| | |
| | 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET |
| | |
| | 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | 2) |
| | . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 / FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |