| 2020-05-21 16:37:25 | PLAN |
| | REVIEW COMMENTS |
| | 4TH REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) COMPLIED. |
| | |
| | 2) NOT COMPLIED. FBC 107.3.5.1.1(8) - PROVIDE WIND |
| | DESIGN LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER |
| | 16. ALSO SPECIFY COMPONENT AND CLADDING PRESSURES FOR |
| | THE ROOF, DOOR AND LOUVER. |
| | THE CERTIFICATE FOR DESIGN LOAD COMPLIANCE THAT WAS |
| | SUBMITTED HAS SOME ISSUES. ITEM #2 IS NOT COMPLETE. |
| | THIS IS AN ENCLOSED STRUCTURE. ITEM #6 SPECIFIES ROOF |
| | PRESSURES FOR THE FLAT ROOF OF +16, -41 FOR ROOF ZONES |
| | 2 AND 3 FOR A RISK CATEGORY II STRUCTURE LOCATED IN |
| | EXPOSURE "C" IN A 170MPH VULT WIND SPEED. PLEASE |
| | EXPLAIN HOW YOU DETERMINED THESE PRESSURES AND PROVIDE |
| | YOUR CALCULATIONS. ITEM # 10 STATES THAT A SOIL TEST |
| | REPORT WAS SUBMITTED. I DID NOT SEE IT WITH THIS |
| | SUBMITTAL. |
| | |
| | 3) NOT COMPLIED. FBC 107.3.4 - PROVIDE TWO SETS OF |
| | PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR THE ROOFING MATERIALS, LOUVERS, FIBER-CEMENT SIDING |
| | AND EXTERIOR DOOR. |
| | THE PRODUCT APPROVALS FOR THE FIBER-CEMENT EXTERIOR |
| | SIDING WAS NOT SUBMITTED. PLEASE MARK THE SPECIFIC |
| | FASTENING OPTION AND IT'S MINIMUM DESIGN PRESSURE ON |
| | THE PRODUCT APPROVAL FOR THE TORCH APPLIED ROOFING |
| | MATERIAL. THE NOA THAT WAS SUBMITTED REQUIRES RAS 117 |
| | CALCULATIONS FROM AN ARCHITECT OR ENGINEER FOR ENHANCED |
| | FASTENING TO MEET HIGHER PRESSURES AT PERIMETER AND |
| | CORNERS AREAS OF THE ROOF. |
| | |
| | 4) NOT COMPLIED. FBC 107.2.1 PROVIDE A ROOF FRAMING |
| | PLAN WITH DETAILS. SPECIFY ROOF TO WALL CONNECTIONS. |
| | THIS WAS NOT ADDRESSED. |
| | |
| | 5) NOT COMPLIED. FBC 107.2.1 PROVIDE A DOOR OPENING |
| | FRAMING DETAIL. THIS WAS NOT PROVIDED. |
| | |
| | 6) NOT COMPLIED. SUBMIT TWO SETS OF THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS FOR THE 1/2" DUROCK SIDING. |
| | FBC 1404.10 THIS WAS NOT PROVIDED. |
| | |
| | 7) NOT COMPLIED. SHOW COMPLIANCE WITH FBC 1403.2 FOR |
| | WEATHER PROTECTION AND 1404.2 FOR WATER-RESISTIVE |
| | BARRIER. THIS WAS NOT ADDRESSED. |
| | |
| | 8) NEW COMMENT. FBC R REQUIRES ROOFS TO HAVE A MINIMUM |
| | 6 INCH OVERHANG OR GUTTERS WITH DOWNSPOUTS. FBC 1503.7 |
| | |
| | 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | |
| | |