Plan Review Notes
Plan Review Notes For Permit 20031057
Permit Number 20031057
Review Stop B
Sequence Number 3
Notes
Date Text
2020-05-18 15:40:58PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN
 LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16. ALSO
 SPECIFY COMPONENT AND CLADDING PRESSURES FOR THE ROOF,
 DOOR AND LOUVER.
 THE CERTIFICATE FOR DESIGN LOAD COMPLIANCE THAT WAS
 SUBMITTED HAS SOME ISSUES. ITEM #2 IS NOT COMPLETE.
 THIS IS AN ENCLOSED STRUCTURE. ITEM #6 SPECIFIES ROOF
 PRESSURES FOR THE FLAT ROOF OF +16, -41 FOR ROOF ZONES
 2 AND 3 FOR A RISK CATEGORY II STRUCTURE LOCATED IN
 EXPOSURE "C" IN A 170MPH VULT WIND SPEED. PLEASE
 EXPLAIN HOW YOU DETERMINED THESE PRESSURES AND PROVIDE
 YOUR CALCULATIONS. ITEM # 10 STATES THAT A SOIL TEST
 REPORT WAS SUBMITTED. I DID NOT SEE IT WITH THIS
 SUBMITTAL.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS,
 LOUVERS, FIBER-CEMENT SIDING AND EXTERIOR DOOR.
 THE PRODUCT APPROVALS FOR THE FIBER-CEMENT EXTERIOR
 SIDING WAS NOT SUBMITTED. PLEASE MARK THE SPECIFIC
 FASTENING OPTION AND IT'S MINIMUM DESIGN PRESSURE ON
 THE PRODUCT APPROVAL FOR THE TORCH APPLIED ROOFING
 MATERIAL. THE NOA THAT WAS SUBMITTED REQUIRES RAS 117
 CALCULATIONS FROM AN ARCHITECT OR ENGINEER FOR ENHANCED
 FASTENING TO MEET HIGHER PRESSURES AT PERIMETER AND
 CORNERS AREAS OF THE ROOF.
  
 4) FBC 107.2.1 PROVIDE A ROOF FRAMING DETAIL. SPECIFY
 ROOF TO WALL CONNECTIONS. THIS WAS NOT ADDRESSED.
  
 5) FBC 107.2.1 PROVIDE A DOOR OPENING FRAMING DETAIL.
 THIS WAS NOT PROVIDED.
  
 6) SUBMIT TWO SETS OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE 1/2" DUROCK SIDING. FBC 1404.10
 THIS WAS NOT PROVIDED.
  
 7) SHOW COMPLIANCE WITH FBC 1403.2 FOR WEATHER
 PROTECTION AND 1404.2 FOR WATER-RESISTIVE BARRIER. THIS
 WAS NOT ADDRESSED.
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  