| 2020-03-25 17:32:15 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.2.5 THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| | AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE, |
| | FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD |
| | ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| | ACCURATE BOUNDARY LINE SURVEY. |
| | |
| | 2) FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN |
| | LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16. ALSO |
| | SPECIFY COMPONENT AND CLADDING PRESSURES FOR THE ROOF, |
| | DOOR AND LOUVER. |
| | |
| | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS, |
| | LOUVERS, FIBER-CEMENT AND EXTERIOR DOOR. |
| | |
| | 4) FBC 107.2.1 PROVIDE A ROOF FRAMING DETAIL. SPECIFY |
| | ROOF TO WALL CONNECTIONS. |
| | |
| | 5) FBC 107.2.1 PROVIDE A DOOR OPENING FRAMING DETAIL. |
| | |
| | 6) SUBMIT TWO SETS OF THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS FOR THE 1/2" DUROCK SIDING. FBC 1404.10 |
| | |
| | 7) SHOW COMPLIANCE WITH FBC 1403.2 FOR WEATHER |
| | PROTECTION AND 1404.2 FOR WATER-RESISTIVE BARRIER. |
| | |
| | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | |
| | |
| | |
| | |
| | |