| 2020-03-23 14:18:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FP 1 - THERE IS NO INDICATION OF A FIRE |
| | SPRINKLER IN THE ELEVATOR PIT. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS. |
| | 8.15.5.1* SIDEWALL SPRAY SPRINKLERS SHALL BE INSTALLED |
| | AT THE BOTTOM |
| | OF EACH ELEVATOR HOISTWAY NOT MORE THAN 2 FT (0.61 M) |
| | ABOVE THE FLOOR OF THE PIT. |
| | 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE |
| | ELEVATOR |
| | HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR |
| | ENCLOSED, NONCOMBUSTIBLE |
| | ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE |
| | HYDRAULIC FLUIDS. |
| | |
| | PLEASE PROVIDE DETAILS OR CORRECT. |
| | |
| | |
| | |
| | 2) SHEET FP 1 - THERE IS AN INDICATION AT THE ENTRY OF |
| | A UTILITY ROOM UNDER THE STAIRS. |
| | |
| | THERE DOES NOT APPEAR TO BE A SPRINKLER HEAD PROTECTING |
| | THIS AREA. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 3) SHEET FP 1 - THERE IS AN INDICATION ON AN ENTRY |
| | AREA. |
| | |
| | THERE DOES NOT APPEAR TO BE SPRINKLER HEAD PROTECTING |
| | THIS AREA. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 4) SHEET FP 3 - THERE IS NO INDICATION OF FIRE |
| | SPRINKLER PROTECTION AT THE TOP OF HOISTWAY |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE |
| | REQUIRED IN ELEVATOR |
| | MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL |
| | SPACES, OR |
| | HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE |
| | WITH THE |
| | APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE |
| | BUILDING |
| | CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL |
| | ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR |
| | IS |
| | DEDICATED TO ELEVATOR EQUIPMENT ONLY. |
| | (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY |
| | SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF |
| | TRACTION |
| | ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER |
| | AUTOMATIC |
| | FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72. |
| | (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL |
| | SPACE, |
| | OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE |
| | REMAINDER |
| | OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/ |
| | CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF |
| | NOT LESS |
| | THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE. |
| | (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE |
| | PERMITTED |
| | TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY |
| | SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF |
| | TRACTION |
| | ELEVATORS. |
| | (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC |
| | TYPE. |
| | 8.15.5.4* AUTOMATIC SPRINKLERS IN ELEVATOR MACHINE |
| | ROOMS OR |
| | AT THE TOPS OF HOISTWAYS SHALL BE OF ORDINARY- OR |
| | INTERMEDIATETEMPERATURE |
| | RATING. |
| | 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY |
| | SPRINKLERS SHALL |
| | BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS. |
| | 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE |
| | ELEVATOR HOISTWAY |
| | BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY |
| | FOR PASSENGER |
| | ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND |
| | THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF |
| | ASME |
| | A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 5) SHEET FP 3 - THERE IS AN INDICATION OF AN OUTDOOR |
| | PORCH OR BALCONY WITH CEILING FANS WITH FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 8.15.7* EXTERIOR PROJECTIONS. |
| | 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3, |
| | OR |
| | 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER |
| | EXTERIOR |
| | PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. |
| | 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | WHERE |
| | THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS |
| | THAT |
| | ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE |
| | RETARDANT? |
| | TREATED WOOD AS DEFINED IN NFPA 703. |
| | 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM BELOW |
| | THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION, |
| | PROVIDED |
| | THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS |
| | ARE NONCOMBUSTIBLE, |
| | LIMITED-COMBUSTIBLE, OR FIRE RETARDANT?TREATED |
| | WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR |
| | PROJECTIONS CONTAIN |
| | ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE |
| | FOLLOWING |
| | UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES: |
| | (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH |
| | NONCOMBUSTIBLE |
| | INSULATION |
| | (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
| | NONCOMBUSTIBLE |
| | OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED |
| | TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE |
| | ENCLOSED |
| | JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME, |
| | INCLUDING |
| | SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR |
| | WITHIN |
| | THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC |
| | [SEE |
| | 11.2.3.1.4(4)(D)] |
| | (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR |
| | PROJECTIONS |
| | NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 6) SHEET FP 3 - SPRINKLER HEAD LOCATION IN THE HALL |
| | INDICATES SEVERAL HEADS THAT APPEAR TO BE TOO CLOSE TO |
| | THE WALL. |
| | |
| | WITH NO DIMENSION INDICATED, PLEAE PROVIDE THE REQUIRED |
| | DIMENSION FROM THE WALL TO AVOID POSSIBLE INSTALLATION |
| | ERROR AND FAILED INSPECTION. |
| | |
| | |
| | |
| | |
| | 7) THERE WE NO MANUFACTURES SPEC SHEETS PROVIDED TO |
| | REVIEW AND VERIFY MATERILAS AND CALCULATIONS. |
| | |
| | PLEASE PROVIDE EQUIPMENT SPEC SHEETS. |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |