Plan Review Notes
Plan Review Notes For Permit 20031048
Permit Number 20031048
Review Stop M
Sequence Number 1
Notes
Date Text
2020-04-06 15:38:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20031048
 4/6/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE NOTE NO NARRATIVE WAS PROVIDED TO ITEMIZE AND
 CLARIFY WHAT CHANGES WERE MADE TO THE APPROVED PLANS-
 SECTION 107.2.1 WPB.
  
 1) SHEET M1.0: IDENTIFY THE NEW ROOM BEING VENTILATED
 BY EF-1 AND A) PROVIDE EXHAUST VENTILATION
 CALCULATIONS. B) PROVIDE THE SEQUENCE OF OPERATION FOR
 THE FAN. C) PROVIDE MAKEUP AIR- SECTION 107.2.1 WPB,
 AND SECTION 501.4 FBC M.
  
 2) M1.0: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 VEF-1 IN THE FIRE PUMP ROOM AND A SEQUENCE OF OPERSTION
 FOR THE FAN. CLARIFY IF THE PUMP IS ELECTRIC OR DIESEL
 POWERED. PLEASE NOTE THAT DIESEL FIRE PUMPS REQUIRE
 CONTINUOUS VENTILATION OPERATION; THE EXHAUST DUCT
 SHALL BE ENCLOSED IN FIRE-RATED CONSTRUCTION FROM THE
 POINT OF PENETRATION OF THE FIRE-RATED WALL TO THE
 EXTERIOR OF THE BUILDING; AND THE FIRE DAMPERS ARE NOT
 PERMITTED- REFER TO SECTIONS 510.7.1 & 510.7.3 FBC M.
  
 3) M1.0: PLEASE SHOW THE RELOCATED CLOTHES DRYER
 EXHAUST DUCT RUNS AND TERMINATION LOCATIONS. SHOW THE
 TOTAL RUN LENGTHS OF THE EXHAUST DUCTS AND VERIFY THEY
 DO NOT EXCEED THE MANUFACTUTRER'S INSTALLATION
 INSTRUCTIONS OR 35'- SEE SECTIONS 504.8.4.1 AND
 504.8.4.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  