| 2020-06-18 13:26:53 | 1) SUBMIT PLUMBING FIXTURE CALCULATIONS FOR THE MINIMUM |
| | NUMBER OF REQUIRED PLUMBING FIXTURES BASED ON THE |
| | OCCUPANT LOADS OF THE DIFFERENT AREAS ON LEVEL 01.PER |
| | MY CALCULATIONS BASED ON THE OCCUPANT LOADS SHOWN ON |
| | SHT.LS1.101, SEPARATE FACILITIES SHALL BE REQUIRED FOR |
| | MALES AND FEMALES PER FBC-PLUMBING SEC.403.2. |
| | 2) PER MY CALCULATIONS AND TABLE 403.1 OF FBC-PLUMBING, |
| | 2 WATER CLOSETS AND 1 LAVATORY ARE REQUIRED FOR THE |
| | MALES AND 3 WATER CLOSETS AND 1 LAVATORY ARE REQUIRED |
| | FOR THE FEMALES FOR LEVEL 01. |
| | 3) SHT. 00.200 - BUILDING TYPE TABLE - THE NOTE AT THE |
| | BOTTOM REFERS TO THE 2010 FBC. REVISE THE NOTE TO READ |
| | 2017 FBC. |
| | 4) SUBMIT FOR ALL THE UNDERSLAB PIPING (SANITARY, |
| | STORM, ETC.) THAT IS GOING TO BE INSTALLED UNDER THIS |
| | FOUNDATION PERMIT. ALSO, TAG ALL RISERS FOR |
| | IDENTIFICATION. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 5) SHT. P2.1B2 - TAG ALL RISERS FOR IDENTIFICATION. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 6) SUBMIT DETAILS AND CALCULATIONS FOR THE LINT |
| | INTERCEPTOR. THE INTERCEPTOR SHALL COMPLY WITH 2017 |
| | FBC-PLUMBING SEC. 103.6. |
| | 7) SHT. LS1.101 - SHOW THE SUBCATEGORY OF THE ASSEMBLY |
| | OCCUPANCY ON THE OCCUPANT LOAD TABLE PER FBC-BUILDING |
| | SEC. 303 AND TABLE 403.1 OF FBC-PLUMBING. |
| | NOTE: THESE PLANS WERE REVIEWED FOR THE PLUMBING FOR |
| | THE FOUNDATION ONLY. A REVIEW WAS NOT PERFORMED FOR |
| | COMPLIANCE WWITH THE FBC-ACCESSIBILITY OR THE FAIR |
| | HOUSING ACT GUIDELINES. COMPLIANCE WITH THESE STANDARDS |
| | WILL BE DONE UNDER THE FULL BUILDING SUBMITTAL REVIEW |
| | ALONG WITH ALL OTHER REQUIRED CODES, STANDARDS AND |
| | REGULATIONS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |