| Date |
Text |
| 2020-05-26 13:48:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1.100 & LS 1.101 - THERE IS AN INDIICATION O |
| | A FFIRE PUMP ROOM; HOWEVER, A FLOOR DRAIN COULD NOT BE |
| | VERIFIED. |
| | |
| | PER NFPA 20 STANDARD FOR THE |
| | INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION |
| | 2013 EDITION |
| | |
| | 4.12.7* DRAINAGE. |
| | 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE |
| | OF ESCAPING |
| | WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP, |
| | DRIVER, CONTROLLER, AND SO FORTH. |
| | 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED |
| | WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE |
| | LOCATION. |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | 2) SHEET C 1. - THERE ARE INDICATION OF UNDERGROUND |
| | FIRE LINES AND FIRE LINE DDCV. |
| | |
| | ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED AND |
| | INSPECTED PER NFPA 24 STANDARD FOR THE INSTALLATION OF |
| | PRIVATE FIRE SERVICE MAINS AND |
| | THEIR APPURTENANCES 2013 EDITION, UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS. |
| | |
| | 1.1 SCOPE. |
| | 1.1.1 THIS STANDARD SHALL COVER THE MINIMUM |
| | REQUIREMENTS |
| | FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND |
| | THEIR APPURTENANCES |
| | SUPPLYING THE FOLLOWING: |
| | (1) AUTOMATIC SPRINKLER SYSTEMS |
| | (2) OPEN SPRINKLER SYSTEMS |
| | (3) WATER SPRAY FIXED SYSTEMS |
| | (4) FOAM SYSTEMS |
| | (5) PRIVATE HYDRANTS |
| | (6) MONITOR NOZZLES OR STANDPIPE SYSTEMS WITH REFERENCE |
| | TO |
| | WATER SUPPLIES |
| | (7) HOSE HOUSES |
| | 1.1.2 THIS STANDARD SHALL APPLY TO COMBINED SERVICE |
| | MAINS |
| | USED TO CARRY WATER FOR FIRE SERVICE AND OTHER USES. |
| | |
| | CHAPTER 4 GENERAL REQUIREMENTS |
| | 4.1* PLANS. |
| | 4.1.1 WORKING PLANS SHALL BE SUBMITTED FOR APPROVAL TO |
| | THE |
| | AUTHORITY HAVING JURISDICTION BEFORE ANY EQUIPMENT IS |
| | INSTALLED |
| | OR REMODELED. |
| | |
| | |
| | PLEASE REVIEW AND ACKNOWLEDGE COMPLIANCE WHERE |
| | APPLICABLE. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |