| 2020-03-24 14:15:23 | |
| | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20030979 |
| | |
| | CODES IN EFFECT: |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SEE BUILDING REVIEWERS COMMENTS. |
| | |
| | 2) PLEASE PROVIDE ENERGY REPORT FOR THE PROPOSED |
| | CONDITIONED SPACE. SEE FBC EC 101.5.1.1.2 |
| | |
| | 3) PROVIDE MANUAL J,S AND D CALCULATIONS FOR THE |
| | PROPOSED NEW SPLIT SYSTEM. SEE FBC RES M1401.3; FBC EC |
| | RE403.7.1 |
| | |
| | 4) OUTDOOR CONDENSING UNIT MUST BE TIED DOWN PER |
| | MANUFACTURE INSTALLATION INSTRUCTIONS OR THE DESIGN |
| | MUST BE STAMPED BY AND ENGINEER. SEE FBC RES M1307.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |