| 2020-03-20 11:02:50 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS THAT WERE SIGNED AND SEALED BY RICHARD |
| | BOYETTE, P.E. WILL HAVE TO BE REVISED TO SHOW THE |
| | STRUCTURAL CHANGES TO THE GARAGE DOOR OPENING IN ORDER |
| | FOR YOU TO INSTALL THE PROPOSED ONE OF A KIND GLASS AND |
| | WOOD PANEL DOORS TO THE OPENING WITH A ROLL DOWN DOOR |
| | FOR HURRICANE PROTECTION. FS 471 |
| | |
| | 2) THE EXTERIOR CUSTOM ONE OF A KIND WOOD FRAMED GLASS |
| | PANEL DOORS WILL REQUIRE SITE SPECIFIC ENGINEERING OR |
| | TESTING BY AN APPROVED TESTING LABORATORY. SUBMIT THE |
| | PRODUCT APPROVAL WITH TEST REPORT OR SIGNED AND SEALED |
| | RATIONAL ANALYSIS AND CALCULATIONS. FBC R609.2.1 |
| | |
| | 3) SUBMIT PLANS WITH DRAWINGS THAT PROVIDE DETAILS AND |
| | CLEARLY SHOW HOW THE PANELS AND HURRICANE PROTECTION |
| | WILL BE INSTALLED. THE PLANS WILL ALSO NEED TO SHOW ANY |
| | MODIFICATIONS OR CHANGES TO THE STRUCTURE OF THE |
| | BUILDING. FBC 107.2.1 |
| | |
| | 4) THE GROUND FLOOR OF THIS BUILDING IS APPROVED AS A |
| | GARAGE OR STORAGE ANY OTHER USE SUCH AS AN OFFICE OR |
| | OTHER TYPE OF HABITABLE SPACE WILL REQUIRE REVISED |
| | PLANS AND ANOTHER IMPACT FEE REVIEW. |
| | |
| | 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | |