| 2020-09-21 08:44:51 | |
| | 3RD REVIEW FBC-2017 RES. |
| | PERMIT- 20030973 |
| | 9/21/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENT #1 FROM THE 1ST AND 2ND REVIEWS STILL EXISTS. A |
| | LARGER TANKLESS WATER HEAT- TITAN N-180- IS NOW SHOWN |
| | ON SHEET P-1, HOWEVER NO SPECS HAVE BEEN SUBMITTED. |
| | THERE IS A COMMENT RESPONSE NARRATIVE SUBMITTED THAT |
| | SHOWS A TEMPERATURE RISE CHART FOR THE N-180. THE CHART |
| | INDICATES A 4.0 GPM FLOW RATE AT 31 DEGREE F |
| | TEMPERATURE RISE. PLEASE NOTE OUR GROUND WATER |
| | TEMPERATURE AVERAGING AROUND 75 DEGREES F WOULD REQUIRE |
| | A MINIMUM OF 31 DEGREE RISE TO REACH HOT WATER |
| | TEMPERATURE OF 110 DEGREES F. A 4.0 GPM FLOW IS |
| | UNDERSIZED FOR THE HOUSE WHICH HAS TWO FULL BATHS, |
| | KITCHEN SINK AND DISHWASHER, AND A WASHING MACHINE. |
| | PLEASE NOTE THAT THE MAX WATER CONSUMPTION FOR FIXTURES |
| | AND FAUCETS ON SHEET P1 IS INCOMPLETE AND DOES NOT |
| | PROVIDE THE TOTAL REQUIRED GPM FLOW FOR THE FIXTURES. |
| | I HAVE TRIED TO CONTACT THE PERSON WHO PREPARED THE |
| | COMMENT RESPONSE NARRATIVE HOWEVER THERE WAS NO CONTACT |
| | INFORMATION- NAME AND TELEPHONE NUMBER- LISTED ON THE |
| | NARRATIVE. |
| | |
| | 1) SHEET P-1 BASED ON THE SUBMITTED SPECIFICATION |
| | SHEET, THE SELECTED TITAN N-120 TANKLESS WATER AT MAX |
| | FLOW OF 4.0 GPM DOES NOT HAVE THE LARGE ENOUGH CAPACITY |
| | TO SUPPLY HOT WATER TO THE FIXTURES SHOWN ON THE PLANS- |
| | SEE TABLE P2903.1 FBC RES. REVISE THE PLAN TO PROVIDE |
| | THE MAKE AND MODEL OF WATER HEATER WITH ADEQUATE |
| | CAPACITY, AND SUBMIT MANUFACTURER?S SPECIFICATIONS WITH |
| | TEMPERATURE RISE AND FLOW CAPACITY CHART. |
| | |
| | 2) SHEET P2, ISOMETRIC: PLEASE LABEL THE WASHING |
| | MACHINE DRAIN AND VENT LINE. TWO SHOWERS ARE INDICATED |
| | HOWEVER BATH 2 HAS A TUB/SHOWER FIXTURE. CHANGE WB |
| | LABELS TO LAVATORIES- SECTION 107.2.1 WPB. |
| | |
| | 3) P-2: PROVIDE A WATER HAMMER ARRESTOR FOR THE SUPPLY |
| | LINE TO THE ICE MAKER- SECTIONS P2903.5 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |