| 2020-08-07 16:06:04 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20030973 |
| | 8/7/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-1 BASED ON THE SUBMITTED SPECIFICATION |
| | SHEET, THE SELECTED TITAN N-120 TANKLESS WATER AT MAX |
| | FLOW OF 4.0 GPM DOES NOT HAVE THE LARGE ENOUGH CAPACITY |
| | TO SUPPLY HOT WATER TO THE FIXTURES SHOWN ON THE PLANS- |
| | SEE TABLE P2903.1 FBC RES. REVISE THE PLAN TO PROVIDE |
| | THE MAKE AND MODEL OF WATER HEATER WITH ADEQUATE |
| | CAPACITY, AND SUBMIT MANUFACTURER?S SPECIFICATIONS WITH |
| | TEMPERATURE RISE AND FLOW CAPACITY CHART. |
| | |
| | 2) P-1: ACCESS TO THE VALVES FOR THE STACKABLE |
| | WASHER/DRYER UNIT REMAINS NOT CLEARLY INDICATED- |
| | SECTION P2903.9.3. TYPICALLY, THE VALVE BOX WOULD BE |
| | LOCATED AT THE FRONT OF THE SIDE WALL TO ALLOW ACCESS. |
| | THE PLAN SHOWS THE BOX AT THE REAR OF THE UNIT WITH A |
| | REMOTE VALVE ALSO SHOWN AT THE REAR. HOW WOULD THE |
| | REMOTE VALVE BE ACCESSED? IF A REMOTE VALVE IS TO BE |
| | INSTALLED, CLEARLY SHOW THE LOCATIONS AND SUBMIT A |
| | PRODUCT SPEC SHEET- SECTION 107.2.1 WPB. |
| | |
| | 3) P-2: A FLAT LINE DRAWING FOR WATER DISTRIBUTION WAS |
| | PROVIDED IN LIEU OF THE REQUEST FOR WATER RISER PER |
| | SECTION 107.3.5.3 WPB. PLEASE REVISE THE DRAWING TO |
| | SHOW THE PIPE SIZES, THE LOCATION AND PIPING FOR THE |
| | WATER HEATER, THE LOCATIONS OF REQUIRED WATER HAMMER |
| | ARRESTORS, AND BACKFLOW PREVENTERS. PLEASE NOTE THAT |
| | WATER HAMMER ARRESTORS ARE REQUIRED FOR SUPPLY LINES TO |
| | QUICK-CLOSING VALVES INCLUDING THE WASHING MACHINE, |
| | DISHWASHER, AND ICE MAKER- SECTION P2903.5 FBC RES. A |
| | BACKFLOW PREVENTER IS REQUIRED FOR THE SUPPLY LINE TO |
| | THE ICE MAKER AND THE DISHWASHER- SECTION P2902.1. THE |
| | DISHWASHER LINE CAN BE PROTECTED USING AN AIR GAP |
| | INSTEAD OF A BF PREVENTER- SECTION P2902.3.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |