| Plan Review Notes For Permit 20030973 |
| Permit Number |
20030973 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-06 08:55:00 | PLUMBING 2ND REVIEW COMMENTS* 20030973 | | | 1) VALUE APPEARS TOO LOW. YOU MUST INCLUDE ALL COST, | | | THIS INCLUDES ALL OWNER SUPPLIED MATERIAL. FBC 109.3 | | | 2) PROVIDE WHICH MODEL TANKLESS YOU ARE USING ON THIS | | | PROJECT. THE HEADING SCR-2 IS NOT LISTED ON THE | | | TEMPERATURE RISE CHART. WITH OUT THIS INFORMATION I AM | | | UNABLE TO VERIFY THE TANKLESS YOU HAVE CHOSEN WILL | | | PRODUCE ENOUGH HOT WATER AT FULL LOAD. FBC-PLB 604.3 | | | 3) BOTH THE FLAT AND ISOMETRIC DRAWING ON SHEETS P1 AND | | | P2 SHOW THE GUEST BATHROOM COMBO FITTING FACING IN THE | | | WRONG DIRECTION. FBC-PLB 706.3 | | | 4) SHOW LOCATION OF WASHING MACHINE REMOTE SHUT OFF | | | VALVES AS IT DOES NOT APPEAR YOU WILL HAVE ACCESS TO | | | THE ONES IN THE WASHING MACHINE BOX WITH IT BEHIND THE | | | STACKABLE WASHER AND DRYER. FBC-PLB 606.3 | | | 5) SHEET ON P1 UNDER TUB AND SHOWER WALL NOTES REFERS | | | TO FBC 2004. PLEASE CORRECT AS WE HAVE BEEN ON THE 2017 | | | 6TH ED SINCE 12/31/2017. FBC 107.2 | | | 6) PROVIDE A WATER ISOMETRIC DRAWING. WPB AD 107.3.5 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | (CAP GOVERNMENT) | | | [email protected] | | | | | | | | | |
|