| 2020-03-25 16:40:55 | ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE EXTERIOR DOOR LANDING FOR THE |
| | SLIDING DOOR AT THE MASTER BED ROOM TO COMPLY WITH FBC |
| | R311.3.2 AND R311.3 |
| | 2) PLEASE SHOW THE EXTERIOR WALL WATER RESISTIVE |
| | BARRIER TO COMPLY WITH FBC R703.2 WATER-RESISTIVE |
| | BARRIER. |
| | ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND |
| | BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR |
| | OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED |
| | OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. |
| | 3) DRAWING A-1 SHOWS ADDITION AS CMU WALL - DRAWING S-1 |
| | SHOWS WOOD FRAMED WALL - PLEASE CLEARIFY - DETAILS |
| | SHOULD MATCH. |
| | 4) PLEASE PROVIDE A TRUSS PLAN SHOWING ANY TRUSS |
| | BRACING REQUIRED. FBC R802.10.3 |
| | 5) PLEASE SHOW WALL AND CEILING INSULATION "R" VALUE |
| | AND INSULATION TYPE TO MATCH OR EXCEED THE "R" VALUE |
| | SHOWN ON THE ENERGY CALCS. |
| | 6) BUILDER PLEASE SIGN THE "ENERGY PERFORMANCE LEVEL |
| | DISPLAY CARD" IN THE SPACE PROVIDED. |
| | 7) OWNER PLEASE SIGN THE ENERGY CALCS. (FORM R405) IN |
| | THE SPACE PROVIDED. |
| | 8) PLEASE PROVIDE THE FRONT PAGES FOR THE "MASONITE" |
| | DOOR PRODUCT APPROVAL (MIAMI DADE OR FLORIDA STATE |
| | FRONT PAGES) |
| | 9) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE USED. |