Plan Review Notes
Plan Review Notes For Permit 20030969
Permit Number 20030969
Review Stop Z
Sequence Number 3
Notes
Date Text
2022-02-16 17:28:51FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. SOME OF THE COMMENTS BELOW
 ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS WELL AS
 WITH THIS PERMIT.
  
 2) UPDATED COMMENT: THANK YOU FOR PROVIDING THE
 ENGINEERING SITE PLANS FOR THE ENTIRE UNDERGROUND
 ELECTRIC PATH; HOWEVER, SURVEY SHEET B-3, WHICH SHOWS
 THE WESTERN PORTION OF THE PROJECT TO THE POWER POLE AT
 MANNING AVENUE WAS NOT INCLUDED WITH THE RESUBMITTAL.
  
 3) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  