| Plan Review Notes For Permit 20030968 |
| Permit Number |
20030968 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-06-30 11:36:04 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | FIRST A FEW QUESTION | | | | | | COVER SHEET SHOWS A PROPOSED POLE WHO WILL INSTALL? | | | | | | SHEET E-2 SHOW APPROXIMATLEY 284' OF UNDERGROUND | | | SERVICE WHO IS INSTALLING THIS CONDUIT AND WIRE? | | | | | | YOUR LETTER FROM FPL GIVES YOU THE 21,100 AVAILABLE | | | FAULT CURRENT IF YOU ARE JUST GOING TO USE THIS AS A | | | BASIS THEN WHAT IS THE AIC RATING OF THE 100A MAIN AND | | | THE BRANCH CIRCUIT BREAKERS. YOU NEED TO STATE THIS ON | | | PANEL SCHEDULE OR AS A NOTE TO THE CONTRACTOR | | | INSTALLING THE PANEL AND BREAKERS. | | | | | | | | | |
|