Plan Review Notes
Plan Review Notes For Permit 20030968
Permit Number 20030968
Review Stop E
Sequence Number 2
Notes
Date Text
2020-06-30 11:36:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FIRST A FEW QUESTION
  
 COVER SHEET SHOWS A PROPOSED POLE WHO WILL INSTALL?
  
 SHEET E-2 SHOW APPROXIMATLEY 284' OF UNDERGROUND
 SERVICE WHO IS INSTALLING THIS CONDUIT AND WIRE?
  
 YOUR LETTER FROM FPL GIVES YOU THE 21,100 AVAILABLE
 FAULT CURRENT IF YOU ARE JUST GOING TO USE THIS AS A
 BASIS THEN WHAT IS THE AIC RATING OF THE 100A MAIN AND
 THE BRANCH CIRCUIT BREAKERS. YOU NEED TO STATE THIS ON
 PANEL SCHEDULE OR AS A NOTE TO THE CONTRACTOR
 INSTALLING THE PANEL AND BREAKERS.
  
  
  