Text |
| 2022-03-15 11:28:16 | FAILED |
| | |
| | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| | PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO |
| | THIS PERMIT BEING APPROVED. SOME OF THE COMMENTS BELOW |
| | ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS WELL AS |
| | WITH THIS PERMIT. |
| | |
| | 2) UPDATED COMMENT: THE RESPONSE STATES THAT FPL WILL |
| | BE UTILIZING THEIR EASEMENT TO INSTALL THE UNDERGROUND |
| | ELECTRIC FROM THE POWER POLE ON PRIVATE PROPERTY TO THE |
| | NEW HANDHOLE IN THE 44TH STREET RIGHT-OF-WAY. YOU MUST |
| | PROVIDE VERIFICATION OF THE EASEMENT. THE BEST METHOD |
| | IS ON A SURVEY; HOWEVER, RECORDED DOCUMENTATION THAT |
| | CLEARLY IDENTIFIES THIS LOCATION IS ALSO ACCEPTABLE. |
| | FPL STATING THEY HAVE AN EASEMENT, DOES NOT VERIFY THAT |
| | THEY HAVE AN EASEMENT. PLEASE NOTE, IF NO EASEMENT |
| | EXISTS, NOTARIZED AUTHORIZATION FROM THE PRIVATE |
| | PROPERTY OWNER FOR THE USE OF THEIR PROPERTY FOR THE |
| | VERIZON UNDERGROUND ELECTRIC IS ALSO ACCEPTABLE. IF NO |
| | EASEMENT IS PRESENT AND YOU ARE UNABLE TO SECURE |
| | AUTHORIZATION FROM THE PRIVATE PROPERTY OWNER, THE |
| | UNDERGROUND ELECTRIC MUST COME FROM AN ALTERNATIVE |
| | LOCATION. |
| | |
| | 3) UPDATED COMMENT: THANK YOU FOR PROVIDING A PARTIAL |
| | CROSS OF THE UNDERGROUND ELECTRIC ALONG 44TH STREET; |
| | HOWEVER, AS THIS IS A CITY RIGHT-OF-WAY, THE CROSS |
| | SECTION NEEDS TO INCLUDE THE ENTIRE BORE LENGTH, NOT A |
| | GAP FOR THE AREA BETWEEN 90 FEET AND 120 FEET. |
| | |
| | 4) BASED ON THE LOCATION OF THE PROPERTY LINE IN |
| | RELATIONSHIP TO THE SIDEWALKS SHOWN ON THE SURVEY, THE |
| | SITE PLAN AND POWER ROUTE PLAN THAT ARE OVERLAID ON THE |
| | AERIAL DO NOT ALIGN. PLEASE REVIEW AND CORRECT. |
| | |
| | 5) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP |
| | 7042 TRAFFIC GREY A. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |