| 2020-04-30 12:36:37 | CONTRACTOR CALLED AND INFORMED ME THAT THIS PROJECT IS |
| | IN A HISTORIC DISTRICT THEREFORE THE ENERGY CALCS AND |
| | MANUAL J IS NOT REQUIRED. THE CONTRACTOR UNDERSTANDS |
| | THAT THE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR |
| | THE TIE DOWN OF THE OUTDOOR APPLIANCE SHALL BE ONSITE |
| | FOR THE INSPECTOR AT FINAL INSPECTION OF THE SYSTEM. |
| 2020-03-20 14:43:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 20030956 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE ENERGY CALCULATIONS BASED ON FBCEC |
| | 101.5.1.1.2 |
| | 2) PLEASE PROVIDE COMPLETE MANUAL S CALCULATIONS FOR |
| | THE HVAC SYSTEM BASED ON FBC RES M1401.3. |
| | 3) PLEASE PROVIDE ORIGINAL SIGNED AND SEALED DRAWINGS |
| | FROM THE ENGINEER FOR THE TIE DOWN OF THE CONDENSING |
| | UNIT. FBC RES M1307.2 |
| | 4) PLEASE PROVIDE GAS LINE DIAGRAM ALONG WITH SPEC |
| | SHEETS OF THE GAS WATER HEATER, ALSO SHOW WHERE THE |
| | FUEL SOURCE IS COMING FROM. FBC FG 402.4.1, 402.4.2, OR |
| | FBC RES G2413.4.1, G2413.4.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED |
| | |