2020-04-01 12:28:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20030953
 4/1/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2.02 & M6.01: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE BATHROOMS AND LOCKER ROOMS- TABLE
 404.3.1.1 FBC M.
  
 2) M5.01 & M6.01: PLEASE INDICATE THE SEQUENCE OF
 OPERATION FOR THE EXHAUST SYSTEM IN THE BATHROOMS AND
 LOCKER ROOMS- SECTIONS 401.3 & 501.4 FBC M.
  
 3) M2.01, M2.02: PLEASE PLACE A NOTE ON THE PLAN TO
 INDICATE THERE IS AN ABOVE CEILING RETURN AIR PLENUM,
 AND NOTE THE RESTRICTIONS ON COMBUSTIBLE MATERIALS IN
 THE SPACE- SECTION 602 FBC M
  
 4) M2.01, M2.02, & M6.01: PLEASE CLARIFY HOW THE RETURN
 AIR PLENUM IS COMMUNICATING WITH THE AIR HANDLER-
 SECTION 601.6. A) INDICATE ON SHEET M2.01 WHICH AIR
 HANDLER OR SYSTEM IS SUPPLYING THE NEW ROOMS AND, AND
 WHICH FAN OR SYSTEM IS EXHAUSTING THE NEW ROOMS-
 SECTION 107.2.1 WPB.
  
 5) M2.02: THERE IS A MISSING FIRE DAMPER AT THE
 PENETRATION OF THE 8" DUCT THROUGH THE SHOWER ROOM
 WALL- SECTION 607.5.2 FBC M.
  
 6) M2.02 & M6.01: THE TRANSFER GRILL DIMENSIONS ON THE
 PLANS DO NOT MATCH THE DIMENSIONS IN THE AIR
 DISTRIBUTION SCHEDULE- SECTION 107.2.1 WPB.
  
 7) M9.03: SHOW ON THE PLAN WHICH DUCT WILL BE FIRE
 WRAPPED PER THE DETAIL ON THE PLAN- SECTION 107.2.1
 WPB.
  
 8) VERIFY THAT THE AIR HANDLER SYSTEM SUPPLYING THE NEW
 OCCUPANCY HAS BEEN EQUIPPED WITH A DUCT SMOKE DETECTOR
 AND IDENTIFY THE LOCATION- SECTION 606.2.1 FBC M.
  
 9) INDICATE IN THE NOTES THAT A TEST AND BALANCE REPORT
 WILL BE PROVIDED FOR FINAL APPROVAL AND OCCUPANCY OF
 THE SPACE- SECTION C408.2.2 FBC EC.
  
 10) SUBMIT AC SYSTEM SIZING CALCULATIONS FOR THE NEW
 TENANT SPACE THAT WAS PREVIOUSLY UNCONDITIONED- SECTION
 C403.2.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  