| 2020-04-01 12:28:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20030953 |
| | 4/1/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M2.02 & M6.01: PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS FOR THE BATHROOMS AND LOCKER ROOMS- TABLE |
| | 404.3.1.1 FBC M. |
| | |
| | 2) M5.01 & M6.01: PLEASE INDICATE THE SEQUENCE OF |
| | OPERATION FOR THE EXHAUST SYSTEM IN THE BATHROOMS AND |
| | LOCKER ROOMS- SECTIONS 401.3 & 501.4 FBC M. |
| | |
| | 3) M2.01, M2.02: PLEASE PLACE A NOTE ON THE PLAN TO |
| | INDICATE THERE IS AN ABOVE CEILING RETURN AIR PLENUM, |
| | AND NOTE THE RESTRICTIONS ON COMBUSTIBLE MATERIALS IN |
| | THE SPACE- SECTION 602 FBC M |
| | |
| | 4) M2.01, M2.02, & M6.01: PLEASE CLARIFY HOW THE RETURN |
| | AIR PLENUM IS COMMUNICATING WITH THE AIR HANDLER- |
| | SECTION 601.6. A) INDICATE ON SHEET M2.01 WHICH AIR |
| | HANDLER OR SYSTEM IS SUPPLYING THE NEW ROOMS AND, AND |
| | WHICH FAN OR SYSTEM IS EXHAUSTING THE NEW ROOMS- |
| | SECTION 107.2.1 WPB. |
| | |
| | 5) M2.02: THERE IS A MISSING FIRE DAMPER AT THE |
| | PENETRATION OF THE 8" DUCT THROUGH THE SHOWER ROOM |
| | WALL- SECTION 607.5.2 FBC M. |
| | |
| | 6) M2.02 & M6.01: THE TRANSFER GRILL DIMENSIONS ON THE |
| | PLANS DO NOT MATCH THE DIMENSIONS IN THE AIR |
| | DISTRIBUTION SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | 7) M9.03: SHOW ON THE PLAN WHICH DUCT WILL BE FIRE |
| | WRAPPED PER THE DETAIL ON THE PLAN- SECTION 107.2.1 |
| | WPB. |
| | |
| | 8) VERIFY THAT THE AIR HANDLER SYSTEM SUPPLYING THE NEW |
| | OCCUPANCY HAS BEEN EQUIPPED WITH A DUCT SMOKE DETECTOR |
| | AND IDENTIFY THE LOCATION- SECTION 606.2.1 FBC M. |
| | |
| | 9) INDICATE IN THE NOTES THAT A TEST AND BALANCE REPORT |
| | WILL BE PROVIDED FOR FINAL APPROVAL AND OCCUPANCY OF |
| | THE SPACE- SECTION C408.2.2 FBC EC. |
| | |
| | 10) SUBMIT AC SYSTEM SIZING CALCULATIONS FOR THE NEW |
| | TENANT SPACE THAT WAS PREVIOUSLY UNCONDITIONED- SECTION |
| | C403.2.1 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |