| Notes |
| Date |
Text |
| 2020-03-20 14:09:56 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | 1) FBC M 301.15/304.1, PROVIDE (ENGINEER APPROVED) TIE | | | DOWN DETAIL FOR THE EXTERIOR CONDENSING UNIT. PLEASE | | | INCLUDE LOCATIONS AND QUANTIES OF FASTENERS AND | | | CONNECTORS IF REQUIRED. | | | 2) FBC M 307.2.4.1, PROVIDE INDICATION OF MINI-SPLIT | | | CHECK VALVE TRAP IN CONDENSATE LINE. | | | 3) FBC M 603.1, PROVIDE INDICATION OF HOW AIR WILL BE | | | CONDITIONED AT OTHER HALF OF HOUSE; WILL THIS BE | | | ACCOMPLISHED THROUGH A SECOND MINI-SPLIT AIR HANDLER? | | | | | | NOTE: A MECHANICAL SUB-PERMIT IS REQUIRED PRIOR TO | | | MECHANICAL WORK. |
|