| Notes |
| Date |
Text |
| 2020-03-20 14:27:56 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FBC B 107, PROVIDE INDICATION ON PLANS OF THE | | | LOCATIONS OF ALL DRYWALL/INSULATION/FRAMING REPAIRS | | | INCLUDING EXTERIOR WALLS. | | | | | | 2) FBC B 107, PROVIDE AN EXTERIOR WALL REPAIR DETAIL ON | | | PLANS, INCLUDING FRAMING MEMBER, INSULATION, AND | | | DRYWALL SPECIFICATIONS. | | | | | | 3) FBC B 107, PROVIDE INDICATION OF LOCATIONS AND | | | DETAILS INCLUDING UL LISTING FOR FIRE RATED TENANT | | | SEPARATION WALLS AND CEILING/FLOOR ASSEMBLIES. | | | | | | 4) FBC B 107, PROVIDE INDICATION OF LOCATION ON PLANS | | | OF WINDOW/DOOR REPLACEMENT. | | | | | | | | | NOTE: ANY WINDOWS OR DOORS THAT ARE NOT IMPACT | | | RESISTANT WILL NEED TO HAVE STORM PROTECTION, SUCH AS | | | SHUTTERS. |
|