| Plan Review Notes For Permit 20030898 |
| Permit Number |
20030898 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-08-04 16:37:38 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-1 | | | | | | RISER DOES NOT SHOW MAIN DISCONNECT AS STATED IN THE | | | NOTES | | | | | | 400A FUSES CAN NOT PROTECT 3/0 AND 1/0 CONDUCTORS UNDER | | | THESE CONDITIONS, FEEDING SUB PANELS MUST BE TAPS? | | | 240.21 WHICH ONE 10' 25' RULE? | | | | | | CONDUCTORS TO FPL COPPER OR ALUMINUMU? | | | | | | VALUE OF PERMIT HAS NOT BEEN ADJUSTED. |
|