| 2020-05-19 15:06:46 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THERE HAS BEEN A SUBSTANTIAL AMOUNT OF WORK ADDED TO |
| | THE PLANS AND YET THE REVISION FORM INDICATES THAT |
| | THERE IS NO INCREASE IN THE VALUE OF WORK PERFORMED. |
| | PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF |
| | WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS FOR |
| | TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC 109.3 |
| | 2. WIRE SPECIFIED IN RISER DIAGRAM FOR FEEL TO FPL IS |
| | NOT SIZED CORRECTLY. FOR A 3 PHASE SERVICE THERE SHOULD |
| | BE A MINIMUM OF 4 WIRES. ADDITIONALLY, THE WIRE MUST BE |
| | SIZED FOR THE MAIN OVERCURRENT PROTECTION, WHICH IS |
| | SHOWN AS 400 AMP. PROVIDE CORRECTION. NEC 250.24(C), |
| | 310.15(B)(16) |
| | 3. RISER DIAGRAM SHOWS FIVE 1/0 CONDUCTORS IN A 2 INCH |
| | CONDUIT TO FEED PANEL C. THIS CONDUIT IS UNDERSIZED. |
| | PROVIDE CORRECTION. NEC INFORMATIVE ANNEX C |
| | 4. LOAD CALCULATION SHOWN DOES NOT MATCH THE LOADS |
| | SHOWN IN PANEL SCHEDULES. PROVIDE ACCURATE LOAD |
| | CALCULATION INCLUDING ALL LOADS. LOAD FOR PANEL C IS |
| | NOT REFLECTED ACROSS ALL PHASES. PROVIDE CORRECTION. |
| | NEC 220 |
| | 5. SHEET E-2 SPECIFIES THE 2011 NEC AS BASIS FOR |
| | DESIGN. THIS IS NOT THE CURRENT CODE. PROVIDE |
| | CORRECTION. FBC PREFACE, ALSO SEE ABOVE. |
| | 6. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9 |
| | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |