| Plan Review Notes For Permit 20030878 |
| Permit Number |
20030878 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-19 14:37:41 | PERMIT NUMBER 20030878 | | | 1. PER FBC 107.2.1, PROVIDE A SANITARY RISER DIAGRAM | | | AND PLAN VIEW SHOWING THE REVISED SANITARY PIPING, | | | VENTS AND FIXTURE LAYOUT TO ACCOMMODATE ALL NEW | | | APPLIANCES AND FIXTURES THAT REQUIRE SANITARY DRAINAGE. | | | 2. PER FBC 107.2.1, PROVIDE A DOMESTIC WATER PLAN VIEW | | | AND ISOMETRIC SHOWING THE REVISED DOMESTIC WATER | | | PIPING, VALVES AND MATERIALS FOR ALL NEW APPLIANCES | | | THAT USE HOT AND COLD WATER. | | | 3. PER FPC 406.2 THE WASTE FROM AN AUTOMATIC CLOTHES | | | WASHER SHALL DISCHARGE THROUGH AN AIR BREAK INTO A | | | STANDPIPE IN ACCORDANCE WITH SECTION 802.3.3 OR INTO A | | | LAUNDRY SINK. THE TRAP AND FIXTURE DRAIN FOR AN | | | AUTOMATIC CLOTHES WASHER STANDPIPE SHALL BE NOT LESS | | | THAN 2 INCHES IN DIAMETER. THE FIXTURE DRAIN FOR THE | | | STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL | | | CONNECT TO A 3 INCH | | | OR LARGER DIAMETER FIXTURE BRANCH OR STACK. | | | |
|