Plan Review Notes
Plan Review Notes For Permit 20030856
Permit Number 20030856
Review Stop P
Sequence Number 1
Notes
Date Text
2020-03-31 15:22:391) SHOW THE LOCATION OF THE WASHING MACHINE ON THE
 PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE FIRST FLOOR 4" VENT IS DRAWN AS A FLAT DRY VENT.
 COMPLY WITH FBC-PLUMBING SEC.905.3.
 3) A CLEANOUT IS REQUIRED IN THE STACKS TO THE 2ND
 FLOOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW