| Plan Review Notes For Permit 20030856 |
| Permit Number |
20030856 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-31 15:22:39 | 1) SHOW THE LOCATION OF THE WASHING MACHINE ON THE | | | PLANS.WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) THE FIRST FLOOR 4" VENT IS DRAWN AS A FLAT DRY VENT. | | | COMPLY WITH FBC-PLUMBING SEC.905.3. | | | 3) A CLEANOUT IS REQUIRED IN THE STACKS TO THE 2ND | | | FLOOR. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|