| Plan Review Notes For Permit 20030788 |
| Permit Number |
20030788 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-22 13:20:21 | THE PREVIOUS FIRE COMMENTS WERE NO SPECIFICALLY | | | ADDRESSED OR THERE ARE NO INDICATIONS THAT WERE | | | CHANGED/CLOUDED ON THE PLAN SHEETS | | | | | | THE PREVIOUS COMMENTS ARE SUBMITTED AGAIN BELOW: | | | | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF A NEW LOUVER ASSEMBLY | | | WITHIN THE WALL HOUSING A FIRE PUMP. | | | | | | THE FIRE PUMP ROOM WALL SHALL HAVE A FIRE RESISTIVE | | | RATING OF 2-HOUR. | | | | | | THERE ARE NO MANUFACTURE SPEC SHEETS OF THE NEW LOUVER | | | INDCATING THE REQUIRED RATING. | | | | | | PER NFPA 20 | | | | | | 4.12.1.1.2* INDOOR FIRE PUMP ROOMS IN NON-HIGH-RISE | | | BUILDINGS | | | OR IN SEPARATE FIRE PUMP BUILDINGS SHALL BE PHYSICALLY | | | SEPARATED OR PROTECTED BY FIRE-RATED CONSTRUCTION IN | | | ACCORDANCE | | | WITH TABLE 4.12.1.1.2. | | | | | | THE TABLE INDICATES IF BOTH THE PUMP ROOM AND ADJACENT | | | STRUCTURES ARE SPRINKLED | | | | | | 1 HOUR FIRE-RATED | | | OR | | | 50 FT (15.3 M) | | | | | | PLEASE PROVIDE DETAILS AND FIRE RATING SPEC SHEETS IF | | | APPLICABLE. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|