| 2020-04-08 18:32:00 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20030721 |
| | 4/8/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE GREASE DUCT INSTALLATION DETAILS: |
| | |
| | A) TYPE OF DUCT MATERIAL AND FABRICATION- SECTIONS |
| | 506.3.1 THROUGH 506..3.2.3 FBC M. |
| | B) DUCT DIMENSIONS- 506.1 |
| | C) DUCT SIZING AND VELOCITY CALCULATIONS- 506.3.4 |
| | |
| | 2) SHOW THE LOCATIONS OF REQUIRED CLEANOUTS AT 20' |
| | VERTICAL SPACING AND HOW ACCESS WILL BE PROVIDED- |
| | SECTION 506.3.8(2) |
| | |
| | A) PROVIDE A CLEANOUT DETAIL- 506.3.8(3,4,5,6,7) |
| | |
| | 3) SHOW THE LOCATION OF THE EXHAUST FAN AND PROVIDE A |
| | FAN SCHEDULE- 506.5.1 THROUGH 506.5.5 |
| | |
| | 4) PROVIDE ENGINEERING FOR ANCHORING AND SUPPORTING THE |
| | ROOF DUCT AND FAN. INCLUDE DETAILS INDICATING THE |
| | CLEARANCE BETWEEN THE DUCT AND THE ROOF SURFACE- |
| | SECTION 301.15 AND 1510.10 FBC B. |
| | |
| | 5) SHEETS M-3,1, 4.1, 4.2, 5.1, 5.2, 5.3, 5.4, 6.1, & |
| | 6.2 ARE INDICATED IN THE MEP NARRATIVE BUT NOT UPLOADED |
| | FOR REVIEW- SECTION 107.2.1 WPB |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |