Plan Review Notes
Plan Review Notes For Permit 20030701
Permit Number 20030701
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-18 12:09:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS NO SITE PLAN INDICATING WHERE THIS TRALIER
 WILL BE LOCATED.
  
 PLEASE PROVIDE AND INDICATED ALL DIMENSIONS TO ALL
 OTHER BUILDINGS/STRUCTURES/PROPERTY LINES
  
  
  
 2) THERE ARE NO INDICATIONS OF ELECTRICAL POWER
 SOURCES.
  
 WILL THERE BE POWER PROVIDED AND WHAT TYPEI.E. FPL,
 GENERATOR AND LOCATION OF SOURCE?
  
  
  
 3) THERE IS NO INDICATION OF A EXIT SIGN WITHIN THE
 TRAILER.
  
 PLEASE PROVIDE DETAILS.
  
  
 4) THERE IS NO INDICASTION OF A FIRE EXTIGUISHER WITHIN
 THE TRAILER.
  
 PLEASE PROVIDE AT LEAST 5LB ABC.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  