| 2020-04-01 07:46:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20030695 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY GAUGE FORM R405 IS MISSING FROM THE |
| | ENERGY COMPLIANCE SUBMITTAL- SECTION R405.2 FBC EC. |
| | |
| | 2) PROVIDE THE MANUAL J WORKSHEETS WITH THE AC SYSTEM |
| | SIZING CALCULATIONS- SECTION R403.7.1 FBC EC. |
| | |
| | 3) PLEASE SHOW A DETAIL OF HOW YOU ARE GOING TO ANCHOR |
| | THE A/C UNIT OUTSIDE. FBC RES M1307.2 ANCHORAGE OF |
| | APPLIANCES. |
| | |
| | 4) THE CONTRACTOR MUST SIGN AND DATE THE DRAWINGS |
| | PROVIDED. FBC WPB- 107.3.4.2 CERTIFICATIONS BY |
| | CONTRACTORS |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |