| Plan Review Notes For Permit 20030675 |
| Permit Number |
20030675 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-18 13:07:15 | 1. NOTE#1: IS INCORRECT AS THE CANDELAS ARE NOT LISTED | | | ON THE PLANS. | | | 2. BASED ON THE PLAN AND COVERAGE AREA PROVIDED, | | | ADDITIONAL DEVICES MAY BE REQUIRED FOR VISUAL | | | NOTIFICATION. | | | 3. SCOPE DICTATES SPRINKLER MONITORING SYSTEM, HOWEVER | | | ALL OTHER NOTES INDICATE FIRE ALARM SYSTEM WITH VOICE | | | COMMUNICATION. PLEASE INDICATE WHICH SYSTEM IS BEING | | | INSTALLED, AND PROVIDE ACCURATE BATTERY AND BATTERY BOX | | | INSTALLATION DIAGRAM. | | | 4. FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND | | | IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER | | | LOCK FOR DEDICATED BRANCH CIRCUIT. | | | 5. A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | | | S. THOMAS | | | 561-804-4728 |
|