Plan Review Notes
Plan Review Notes For Permit 20030675
Permit Number 20030675
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-18 13:07:151. NOTE#1: IS INCORRECT AS THE CANDELAS ARE NOT LISTED
 ON THE PLANS.
 2. BASED ON THE PLAN AND COVERAGE AREA PROVIDED,
 ADDITIONAL DEVICES MAY BE REQUIRED FOR VISUAL
 NOTIFICATION.
 3. SCOPE DICTATES SPRINKLER MONITORING SYSTEM, HOWEVER
 ALL OTHER NOTES INDICATE FIRE ALARM SYSTEM WITH VOICE
 COMMUNICATION. PLEASE INDICATE WHICH SYSTEM IS BEING
 INSTALLED, AND PROVIDE ACCURATE BATTERY AND BATTERY BOX
 INSTALLATION DIAGRAM.
 4. FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND
 IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER
 LOCK FOR DEDICATED BRANCH CIRCUIT.
 5. A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  