| 2020-03-27 11:55:44 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-1, MP-1- TUB BOX INFILL: PROVIDE A UL TESTED |
| | AND APPROVED FIRESTOPPING ASSEMBLY FOR THE DRAIN PIPE |
| | PENTRATION THROUGH THE FIRE-RATED FLOOR/CEILING |
| | ASSEMBLY- SECTION 714.4.1 FBC B. THE PIPE SHALL ALSO BE |
| | PROTECTED FROM CORROSION BY SHEATHING OR WRAPPING IN |
| | ACCORDANCE WITH SECTION 305.1 FBC P. |
| | |
| | 2) MP-1: PLEASE UPDATE THE CODE COMPLIANCE DATA TO |
| | INDICATE THE FLORIDA PLUMBING CODE SIXTH EDITION 2017, |
| | AND REMOVE THE FBC RES P2709.1 REFERENCE FROM THE |
| | SHOWER DETAIL. THIS PROJECT IS NOT GOVERNED BY THE |
| | SINGLE-FAMILY RESIDENTIAL CODE BECAUSE IT A MULTI-STORY |
| | R-2 OCCUPANCY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |