| Plan Review Notes For Permit 20030645 |
| Permit Number |
20030645 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-16 14:59:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF THIS BE A LOCAL SYSTEM | | | ONLY. THERE IS NO INDICATION OF WHAT TYPE OF FIRE ALARM | | | SYSTEM IS EXISTING. | | | | | | PER NFPA 1 AND 101 | | | | | | 13.7.1.9.2.1* ELEVATOR LOBBY, HOISTWAY, AND ASSOCIATED | | | MACHINE | | | ROOM SMOKE DETECTORS USED SOLELY FOR ELEVATOR RECALL, | | | AND HEAT | | | DETECTORS USED SOLELY FOR ELEVATOR POWER SHUTDOWN, | | | SHALL NOT BE | | | REQUIRED TO ACTIVATE THE BUILDING EVACUATION ALARM IF | | | THE POWER | | | SUPPLY AND INSTALLATION WIRING TO SUCH DETECTORS ARE | | | MONITORED BY | | | THE BUILDING FIRE ALARM SYSTEM, AND IF THE ACTIVATION | | | OF SUCH | | | DETECTORS INITIATES A SUPERVISORY SIGNAL AT A | | | CONSTANTLY ATTENDED | | | LOCATION. [101: 9.6.3.2.1] | | | | | | PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|