| Plan Review Notes For Permit 20030640 |
| Permit Number |
20030640 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-04-14 11:17:55 | KIOSK | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) KIOSK DRAWINGS GL1 THROUGH GL13 - GENERAL NOTE | | | NUMBER 5 SAYS "PERIMETER FASTENERS SHALL BE AS NOTED | | | HEREON" . DRAWINGS DO NOT SHOW FASTENER TYPE, SIZE, | | | AMOUNT, ON CENTER SPACING ETC. THIS INFORMATION NEEDS | | | TO BE ON THE DRAWINGS. | | | 2) NEED COMPLETE (FRONT PAGES AND THE INSTALLATION | | | INSTRUCTIONS) COPIES OF THE PRODUCT APPROVALS THAT ARE | | | MENTIONED ON THE DRAWINGS. | | | 3) PLEASE REMOVE ALL NOTES THAT SAY "PRE FAB BUILDING" | | | FROM ALL DRAWINGS. | | | 4) KIOSK DRAWINGS GL1 THRU GL13 DO NOT SHOW AS | | | ELECTRONICALLY SIGNED IN "ADOBE". | | | |
|