| Plan Review Notes For Permit 20030640 |
| Permit Number |
20030640 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-26 15:47:45 | PRE FAB KIOSK | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE STATE APPROVED MANUFACTURED BUILDING | | | DRAWINGS (MARKED REVIEWED AND APPROVED BY A 3RD PARTY) | | | OR PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT | | | APPROVAL FOR THE ENTIRE BUILDING. FBC WPB AMENDMENTS | | | 107.3 EXCEPTIONS. | | | 2) IF THE BUILDING IS BEING BUILT ON SITE THE DRAWINGS | | | WILL NEED TO SHOW ALL CONNECTIONS, COLUMN AND BEAM | | | DESIGNATIONS, PROVIDE ALL PRODUCT APPROVALS FOR ALL | | | STOREFRONT GLAZING, DOORS AND WINDOWS. | | | 3) DRAWING A1.1.1 SHOWS COUNTER HEIGHT AT 34 INCHES - | | | DRAWING A3.0.1 SHOWS COUNTER HEIGHT AT 36 INCHES - | | | PLEASE CLARIFY TO COMPLY WITH FBC ACCESSIBILITY. | | | | | | |
|