| Plan Review Notes For Permit 20030637 |
| Permit Number |
20030637 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-26 12:16:07 | 1. 2017FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR | | | BUILDINGS. | | | THE SCOPE OF THIS WORK IS UNCLEAR. THERE ARE NO | | | DEMOLITION DRAWINGS SO IT IS UNKNOWN IF THIS IS AN AIR | | | CONDITIONING REPLACEMENT PROJECT OR THESE ARE NEW UNITS | | | ETC. ARE UNITS ABOVE CEILING OR IN A MER. ALSO THERE | | | ARE NO OUTSIDE AIR VENTILATION CALCULATIONS BASED ON | | | THE NUMBER OF PEOPLE FOR THIS OCCUPANCY. IS THE OUTSIDE | | | AIR DUCT INSULATED THAT IS BRINGING IN OUTSIDE AIR TO | | | THE FCU'S? I SEE M.O.D.'S ARE INSTALLED AT THE FCU'S IN | | | THE O.A. DUCTS. IS O.A. ALLOWED TO MIGRATE INTO THE | | | BUILDING. IT IS UNCLEAR HOW THIS IS SUPPOSED TO WORK. | | | PLEASE DESCRIBE IN DETAIL THE EXISTING SYSTEMS AND WHAT | | | EXACTLY IS TAKING PLACE IN THE SCOPE OF YOUR WORK. | | | THERE ARE NO OBVIOUS ROOMS CALLED OUT OR NUMBERED ETC. | | | | | | PLEASE PROVIDE A COMMENT/RESPONSE LETTER WITH YOUR | | | RESUBMITTAL AND FURTHER COMMENTS MAY BE MADE AT THAT | | | TIME | | | | | | REVIEWED REMOTELY BY JAMES BAKER, PE | | | PX3997, PE77268 | | | 561-805-6724 | | | [email protected] | | | | | | |
|