| Plan Review Notes For Permit 20030581 |
| Permit Number |
20030581 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-07-12 16:08:33 | BUILDING PROVISO: | | | SHEET A-103. THE CONDENSING UNIT STAND IS TO CARRY AN | | | NOA OR HAVE A | | | STTRUCTURAL WIND LOADING ANALYSIS COMPLETE WITH | | | ATTACHMENT DETAILS. THE | | | UNIT TO STAND AND STAND TO ROOF ATTACHMENT SHALL BE PER | | | THE NOA OR STRUCTURAL | | | ENGINEERING CALCULATION/ INSTRUCTIONS. THE NOA OR | | | STRUCTURAL CALCULATIONS | | | MUST BE PROVIDED TO THE ENGINEER OF RECORD FOR APPROVAL | | | AND TOTHE BUILDING | | | DEPARTMENT FOR APPROVAL PRIOR TO CALLING FOR THE FIRST | | | INSPECTION. | | | BUILD. REVIEW J. WITMER | | | |
|