Plan Review Notes
Plan Review Notes For Permit 20030569
Permit Number 20030569
Review Stop R
Sequence Number 5
Notes
Date Text
2021-08-24 11:51:30ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = NEED TO
 CHOOSE A ROOFING SYSTEM IN THE PRODUCT APPROVAL (FROM
 PAGE 8 TO PAGE18) THAT SHOWS THE REQUIRED WIND DESIGN
 PRESSURE OF (108 PSF PER FBC R TABLE 301.2 (2)) -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE ADDITIONAL
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND
 PRESSURE THEN THE CHOSEN ROOFING SYSTEM - SEE GENERAL
 LIMITATION NOTES ON THE PRODUCT APPROVAL.
  