Plan Review Notes
Plan Review Notes For Permit 20030565
Permit Number 20030565
Review Stop P
Sequence Number 3
Notes
Date Text
2020-10-07 15:32:5310/07/20 3RD PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE SANITARY RISER DIAGRAM, SOME ITEMS NEED
 CORRECTIONS AS FOLLOW;
  
 A. SHEET P 7.5 2VD, 2V2C, 2V2D, V1A, AND V2A BATHROOM
 SHOWER IS NOT VENTED CORRECTLY, PLEASE REFER TO 2V2A
 FOR A CORRECT METHOD, PER THE 2017 FBC SEC. P910.1.
  
 B. SHEET P7.6 SHOWER ON S2A AND 2SA2 NEED TO BE VENTED
 BETWEEN SHOWER AND WATER CLOSET WITH LAV RISER PER THE
 2017 FBC SEC. P910.1.
  
 C. SHEET P7.7 SHOWER ON 2V2A NEEDS TO BE VENTED BETWEEN
 SHOWER AND WATER CLOSET WITH LAV RISER, REFER TO S1A
 FOR A CORRECT METHOD, PER THE 2017 FBC SEC. P910.1.
  
 D. SHEET P7.8 THE DIRECTION OF FLOW FROM BRANCH TO THE
 SHOWER IS NOT CORRECT ON 2S2B AND S2B PER THE 2017 FBC
 SEC. P706.1. SHOWER ON 2S2B AND S2B NEED TO BE VENTED
 BETWEEN THE SHOWER AND WATER CLOSET WITH A LAV RISER
 PER THE 2017 FBC SEC. P910.1.
  
 E. SHEET P7.9 THE DIRECTION OF FLOW FROM BRANCH TO THE
 SHOWER IS NOT CORRECT ON S2C AND 2S2C PER THE 2017 FBC
 SEC. P706.1. SHOWER ON S2C AND 2S2C NEED TO BE VENTED
 BETWEEN THE SHOWER AND WATER CLOSET WITH A LAV RISER
 PER THE 2017 FBC SEC. P910.1.
  
 F. SHEET P7.10 THE DIRECTION OF FLOW FROM BRANCH TO THE
 SHOWER IS NOT CORRECT ON S2D AND 2S2D PER THE 2017 FBC
 SEC. P706.1. SHOWER ON S2D AND 2S2D NEED TO BE VENTED
 BETWEEN THE SHOWER AND WATER CLOSET WITH A LAV RISER
 PER THE 2017 FBC SEC. P910.1. SHOWER S2D WAS CHANGED ON
 THE 2ND FLOOR BUT NOT ON 3RD AND IT NEEDS TO BE MOVED
 TO THE BATHROOM GROUP OF V2D PER THE 2017 FBC. SEC.
 P706.1.
  
 2. SHEET P7.3 THEIR OS A DRY VENT AT THE END OF THE
 BATHROOM UPSTREAM FROM WATER FOUNTAIN THAT IS NOT
 REQUIRED AS IT CAN NOT BE MADE A WET VENT YOU CAN
 DELETE IT PER THE 2017 FBC SEC. P317.
  
 PLEASE NOTE IF YOU WOULD SEND ME YOUR CORRECTION BY
 EMAIL I WILL REVIEW AND REDLINE BEFORE YOU UPLOAD THEM
 TO PROJECTDOC TO HAVE CORRECTIONS REFLECT WHAT THE
 COMMENT REQUEST.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  