| Date |
Text |
| 2020-08-14 13:23:17 | 08/14/20 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE ELEVATOR A IS HYDRAULIC TYPE AND IT REQUIRES A |
| | PUMP WHERE OIL IS PRESENT OR ALARM, PLEASE DETAILS |
| | LOCATION AND WHERE DRAINED PER THE 2017 FBC SEC. P |
| | 712.3. IF A SUMP PUMP WILL BE INSTALLED IN THE ELEVATOR |
| | SUMP, THE INSTALLATION SHALL COMPLY WITH FBC-PLUMBING |
| | SEC.1003.4. |
| | |
| | 2. IN THE UNDERGROUND SANITARY RISER DIAGRAM, SOME |
| | ITEMS NEED CORRECTIONS AS FOLLOW; |
| | |
| | A. SHEET. P7.2 - DETAIL #1 - A MAXIMUM OF 10 FIXTURE |
| | UNITS SHALL BE VENTED BY A 1 1/2 INCH VENT PER |
| | FBC-PLUMBING TABLE 906.1. AS DRAWN, 15 FIXTURE UNITS |
| | ARE BEING VENTED BY THE 1 1/2 INCH VENT. REFER TO |
| | FBC-PLUMBING TABLE 709.1 FOR FIXTURE UNIT VALUE FOR A |
| | BATHROOM GROUP, TAG VENT RISER ON TYPICAL #3 IF |
| | APPLICABLE. |
| | |
| | B. SHEET P 7.3 DIRECTION OF FLOW ON RISER 4" WHICH IS |
| | ALSO MISSING A TAG ON 2- 4" AND 1 1/2" (SANITARY AND |
| | WATER) PER THE 2017 FBC SEC. 706.1. THE DRINKING |
| | FOUNTAIN ON WATER RISER REQUIRES A HAMMER ARRESTOR PER |
| | THE 2017 FBC SEC. P604.9. THE LINE TO FEED THE DRINKING |
| | FOUNTAIN IS 1 1/2" AND IT SHOULD SAY 1/2" PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. SHEET P 7.5 DIRECTION OF FLOW FROM S2A TO 2V2C/2VB. |
| | SHOWER ON 4" S2D NEEDS TO BE MOVED TO THE BATHROOM |
| | GROUP OF V2D PER THE 2017 FBC SEC. P706.1. KITCHEN SINK |
| | K1A ON BOTH SIDES NEEDS TO BE DOWNSTREAM FROM BATHROOM |
| | GROUP WET VENT PER THE 2017 FBC SEC. P915.1. SHOWER ON |
| | 2V2A NEEDS TO BE VENTED BETWEEN SHOWER AND WATER CLOSET |
| | WITH LAV RISER PER THE 2017 FBC SEC. P910.1. |
| | |
| | D. SHEET P 7.6 P SHOWER ON A2A NEEDS TO BE VENTED |
| | BETWEEN SHOWER AND WATER CLOSET WITH LAV RISER PER THE |
| | 2017 FBC SEC. P910.1. PLEASE LABEL ALL RE-VENTS PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | E. SHEET P 7.7 SHOWER ON S1A NEEDS TO BE VENTED BETWEEN |
| | SHOWER AND WATER CLOSET WITH LAV RISER PER THE 2017 FBC |
| | SEC. P910.1. PLEASE LABEL ALL RE-VENTS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | F. SHEET P 7.8 DIRECTION OF FLOW FROM S2B RISER GOING |
| | TO BATHROOM GROUP PER THE 2017 FBC SEC. P706.1. SHOWER |
| | ON 2V2B NEEDS TO BE VENTED BETWEEN SHOWER AND WATER |
| | CLOSET WITH LAV RISER PER THE 2017 FBC SEC. P910.1. |
| | PLEASE LABEL ALL RE-VENTS PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | G. SHEET P 7.10 SHOWER S2D NEEDS TO BE MOVED TO THE |
| | BATHROOM GROUP OF V2D PER THE 2017 FBC SEC. P706.1. |
| | PLEASE LABEL ALL RE-VENTS PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE IDENTIFY THE TUBS AS TUBS ON THE RISER |
| | DIAGRAMS AND NOT AS SHOWERS. |
| | |
| | 4. PLEASE CHECK ALL THE RISER TAGS ON THE PLAN VIEW |
| | SHEETS AGAINST THE SANITARY RISER DIAGRAMS TO ENSURE |
| | THE RISER TAGS CORRELATE THROUGH EACH FLOOR. REFER TO |
| | SHEETS P7.3, P7.4, P7.5, P7.6 & P7.7, 7.8, P7.9, AND |
| | 7.10 PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. THERE |
| | TOO MANY TO MENTION SO PLEASE RECTIFY TO PREVENT |
| | FURTHER REVIEWS, THANK YOU. |
| | |
| | 5. FLOOR DRAIN REQUIRES A TRAP PRIMER PLEASE PROVIDE |
| | HOW YOU ARE GOING TO PROTECT THE TRAP SEAL PER THE 2017 |
| | FBC SEC. 1002.4.1. |
| | |
| | 6. PLEASE PROVIDE INFORMATION ON SHEET P 5.6 ON THE |
| | COFFEE MAKER OF A VACUUM BREAKER OF A DUAL CHECK VALVE |
| | THAT COMPLIES WITH ASSE 1024 PER THE 2017 FBC SEC. |
| | P608.16.10. |
| | |
| | 7. PLEASE NOTE ON SHEET P 5.6 MOP SINK WALLS SHALL BE |
| | IMPERVIOUS 18? PER THE 2017 FBC B 1210.2.2. |
| | |
| | 8. SHEET P 5.6 TEMPERED WATER IS REQUIRED TO THE |
| | LAVATORY IN THE COMMON AREA TOILET ROOM PER 2017 FBC |
| | PLUMBING SEC. 416.5, 607.1, A NOTE WAS PUT IN FOR |
| | INSTANT HOT. THE TEMPERED WATER MUST BE A DEVICE THAT |
| | COMPLIES WITH ASSE 1070 PER THE 2017 FBC SEC. P607.1.2, |
| | PLEASE UPDATE THE NOTE. |
| | |
| | 9. THE 1 1/2" VENT FOR TOILET AND LAV IS DRY NEEDS TO |
| | BE A WET VENT PER 2017 FBC SEC. P912.2. |
| | |
| | 10. PLEASE PROVIDE A RISER FOR PAN AND CONDENSATE LINE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) |
| | COMMERCIAL PLUMBING AND 2017 FBC SEC. P317. |
| | |
| | 11. DRINKING FOUNTAIN LOCATION SHALL HAVE ACCESS TO |
| | RESIDENCE AND VISITORS WITH AN UNRESTRICTED OPEN AREA |
| | PLEASE SHOW A LOCATION OPEN TO ALL PATRIATES PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) |
| | COMMERCIAL PLUMBING. |
| | |
| | 12. FIRESTOPPING DETAILS HAVE BEEN SUBMITTED FOR METAL |
| | PIPE THROUGH RATED WALLS AND FLOORS. IF PVC PIPE IS TO |
| | BE INSTALLED, SUBMIT FIRE-STOPPING ASSEMBLY DETAILS FOR |
| | THE PVC PIPE THROUGH RATED FLOORS AND WALLS PER THE WPB |
| | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.1. |
| | |
| | 13. THIS IS A 2ND REQUEST THE PRESSURE CYLINDER FOR THE |
| | ELEVATOR SHALL BE PROTECTED IN ACCORDANCE WITH 2017 |
| | FBC-BUILDING SEC.3011. I COULD NOT FIND THIS DETAIL ON |
| | THE PLANS. PLEASE SUBMIT THE SPECIFIC PAGE WHERE THIS |
| | DETAIL CAN BE FOUND. |
| | |
| | 14. SHT.A-0.1 - DETAIL #3 - UNIT 2A - THIS LAYOUT DOES |
| | NOT COMPLY WITH THE FAIR HOUSING ACT DESIGN MANUAL, |
| | CHAPTER 7, PAGE 7.56 & 7.57. THE ONLY FIXTURE PERMITTED |
| | TO BE ADJACENT TO THE SHOWER IS A LAVATORY MOUNTED ON |
| | THE CONTROL WALL BESIDE THE SHOWER AND MAY OVERLAP THE |
| | CLEAR FLOOR SPACE BY A MAXIMUM OF 6 INCHES. THE PORTION |
| | OF THE LAVATORY THAT OVERLAPS THE CLEAR FLOOR SPACE |
| | MUST HAVE KNEE SPACE BELOW OR A REMOVABLE VANITY |
| | CABINET. A 30 INCH WIDE BY 48 INCHES DEEP CLEAR FLOOR |
| | SPACE MUST BE PROVIDED PARALLEL TO THE SHOWER AND FLUSH |
| | WITH THE CONTROL WALL THIS IS A 2ND REQUEST. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |