Plan Review Notes
Plan Review Notes For Permit 20030565
Permit Number 20030565
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-14 13:23:1708/14/20 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE ELEVATOR A IS HYDRAULIC TYPE AND IT REQUIRES A
 PUMP WHERE OIL IS PRESENT OR ALARM, PLEASE DETAILS
 LOCATION AND WHERE DRAINED PER THE 2017 FBC SEC. P
 712.3. IF A SUMP PUMP WILL BE INSTALLED IN THE ELEVATOR
 SUMP, THE INSTALLATION SHALL COMPLY WITH FBC-PLUMBING
 SEC.1003.4.
  
 2. IN THE UNDERGROUND SANITARY RISER DIAGRAM, SOME
 ITEMS NEED CORRECTIONS AS FOLLOW;
  
 A. SHEET. P7.2 - DETAIL #1 - A MAXIMUM OF 10 FIXTURE
 UNITS SHALL BE VENTED BY A 1 1/2 INCH VENT PER
 FBC-PLUMBING TABLE 906.1. AS DRAWN, 15 FIXTURE UNITS
 ARE BEING VENTED BY THE 1 1/2 INCH VENT. REFER TO
 FBC-PLUMBING TABLE 709.1 FOR FIXTURE UNIT VALUE FOR A
 BATHROOM GROUP, TAG VENT RISER ON TYPICAL #3 IF
 APPLICABLE.
  
 B. SHEET P 7.3 DIRECTION OF FLOW ON RISER 4" WHICH IS
 ALSO MISSING A TAG ON 2- 4" AND 1 1/2" (SANITARY AND
 WATER) PER THE 2017 FBC SEC. 706.1. THE DRINKING
 FOUNTAIN ON WATER RISER REQUIRES A HAMMER ARRESTOR PER
 THE 2017 FBC SEC. P604.9. THE LINE TO FEED THE DRINKING
 FOUNTAIN IS 1 1/2" AND IT SHOULD SAY 1/2" PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. SHEET P 7.5 DIRECTION OF FLOW FROM S2A TO 2V2C/2VB.
 SHOWER ON 4" S2D NEEDS TO BE MOVED TO THE BATHROOM
 GROUP OF V2D PER THE 2017 FBC SEC. P706.1. KITCHEN SINK
 K1A ON BOTH SIDES NEEDS TO BE DOWNSTREAM FROM BATHROOM
 GROUP WET VENT PER THE 2017 FBC SEC. P915.1. SHOWER ON
 2V2A NEEDS TO BE VENTED BETWEEN SHOWER AND WATER CLOSET
 WITH LAV RISER PER THE 2017 FBC SEC. P910.1.
  
 D. SHEET P 7.6 P SHOWER ON A2A NEEDS TO BE VENTED
 BETWEEN SHOWER AND WATER CLOSET WITH LAV RISER PER THE
 2017 FBC SEC. P910.1. PLEASE LABEL ALL RE-VENTS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. SHEET P 7.7 SHOWER ON S1A NEEDS TO BE VENTED BETWEEN
 SHOWER AND WATER CLOSET WITH LAV RISER PER THE 2017 FBC
 SEC. P910.1. PLEASE LABEL ALL RE-VENTS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. SHEET P 7.8 DIRECTION OF FLOW FROM S2B RISER GOING
 TO BATHROOM GROUP PER THE 2017 FBC SEC. P706.1. SHOWER
 ON 2V2B NEEDS TO BE VENTED BETWEEN SHOWER AND WATER
 CLOSET WITH LAV RISER PER THE 2017 FBC SEC. P910.1.
 PLEASE LABEL ALL RE-VENTS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. SHEET P 7.10 SHOWER S2D NEEDS TO BE MOVED TO THE
 BATHROOM GROUP OF V2D PER THE 2017 FBC SEC. P706.1.
 PLEASE LABEL ALL RE-VENTS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE IDENTIFY THE TUBS AS TUBS ON THE RISER
 DIAGRAMS AND NOT AS SHOWERS.
  
 4. PLEASE CHECK ALL THE RISER TAGS ON THE PLAN VIEW
 SHEETS AGAINST THE SANITARY RISER DIAGRAMS TO ENSURE
 THE RISER TAGS CORRELATE THROUGH EACH FLOOR. REFER TO
 SHEETS P7.3, P7.4, P7.5, P7.6 & P7.7, 7.8, P7.9, AND
 7.10 PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. THERE
 TOO MANY TO MENTION SO PLEASE RECTIFY TO PREVENT
 FURTHER REVIEWS, THANK YOU.
  
 5. FLOOR DRAIN REQUIRES A TRAP PRIMER PLEASE PROVIDE
 HOW YOU ARE GOING TO PROTECT THE TRAP SEAL PER THE 2017
 FBC SEC. 1002.4.1.
  
 6. PLEASE PROVIDE INFORMATION ON SHEET P 5.6 ON THE
 COFFEE MAKER OF A VACUUM BREAKER OF A DUAL CHECK VALVE
 THAT COMPLIES WITH ASSE 1024 PER THE 2017 FBC SEC.
 P608.16.10.
  
 7. PLEASE NOTE ON SHEET P 5.6 MOP SINK WALLS SHALL BE
 IMPERVIOUS 18? PER THE 2017 FBC B 1210.2.2.
  
 8. SHEET P 5.6 TEMPERED WATER IS REQUIRED TO THE
 LAVATORY IN THE COMMON AREA TOILET ROOM PER 2017 FBC
 PLUMBING SEC. 416.5, 607.1, A NOTE WAS PUT IN FOR
 INSTANT HOT. THE TEMPERED WATER MUST BE A DEVICE THAT
 COMPLIES WITH ASSE 1070 PER THE 2017 FBC SEC. P607.1.2,
 PLEASE UPDATE THE NOTE.
  
 9. THE 1 1/2" VENT FOR TOILET AND LAV IS DRY NEEDS TO
 BE A WET VENT PER 2017 FBC SEC. P912.2.
  
 10. PLEASE PROVIDE A RISER FOR PAN AND CONDENSATE LINE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING AND 2017 FBC SEC. P317.
  
 11. DRINKING FOUNTAIN LOCATION SHALL HAVE ACCESS TO
 RESIDENCE AND VISITORS WITH AN UNRESTRICTED OPEN AREA
 PLEASE SHOW A LOCATION OPEN TO ALL PATRIATES PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING.
  
 12. FIRESTOPPING DETAILS HAVE BEEN SUBMITTED FOR METAL
 PIPE THROUGH RATED WALLS AND FLOORS. IF PVC PIPE IS TO
 BE INSTALLED, SUBMIT FIRE-STOPPING ASSEMBLY DETAILS FOR
 THE PVC PIPE THROUGH RATED FLOORS AND WALLS PER THE WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.1.
  
 13. THIS IS A 2ND REQUEST THE PRESSURE CYLINDER FOR THE
 ELEVATOR SHALL BE PROTECTED IN ACCORDANCE WITH 2017
 FBC-BUILDING SEC.3011. I COULD NOT FIND THIS DETAIL ON
 THE PLANS. PLEASE SUBMIT THE SPECIFIC PAGE WHERE THIS
 DETAIL CAN BE FOUND.
  
 14. SHT.A-0.1 - DETAIL #3 - UNIT 2A - THIS LAYOUT DOES
 NOT COMPLY WITH THE FAIR HOUSING ACT DESIGN MANUAL,
 CHAPTER 7, PAGE 7.56 & 7.57. THE ONLY FIXTURE PERMITTED
 TO BE ADJACENT TO THE SHOWER IS A LAVATORY MOUNTED ON
 THE CONTROL WALL BESIDE THE SHOWER AND MAY OVERLAP THE
 CLEAR FLOOR SPACE BY A MAXIMUM OF 6 INCHES. THE PORTION
 OF THE LAVATORY THAT OVERLAPS THE CLEAR FLOOR SPACE
 MUST HAVE KNEE SPACE BELOW OR A REMOVABLE VANITY
 CABINET. A 30 INCH WIDE BY 48 INCHES DEEP CLEAR FLOOR
 SPACE MUST BE PROVIDED PARALLEL TO THE SHOWER AND FLUSH
 WITH THE CONTROL WALL THIS IS A 2ND REQUEST.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720