| 2020-08-04 15:51:01 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20030565 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SEE 1ST CYCLE REVIEW COMMENTS 12,13,14 AND |
| | MAKE SURE THIS HAS BEEN COMPLETED. PLEASE UPLOAD THE |
| | CORRECT DOCUMENTS FOR BUILDING B ONLY; ELEVATOR MACHINE |
| | ROOM LOAD CALS STILL SHOW BIKE ROOM AND BUILDING A; |
| | UNIT 1A1 LOAD CALCS V2 IN PROJECT INFORMATION (NOTES) |
| | STILL SHOWS BUILDING A-UNIT 1A 1ST FLOOR. UNIT 1A2 LOAD |
| | CALCS V2 SHEET 3 UNDER PROJECT INFORMATION (NOTES) |
| | PLEASE SHOW THE CORRECT BUILDING (B).UNIT 2A1 EWN LOAD |
| | CALCS- PLEASE IDENTIFY WHICH BUILDING. PLEASE RECHECK |
| | ALL LOAD CALCULATION SHEETS AND ENERGY CALCULATION |
| | SHEETS TO VERIFY THEY HAVE THE CORRECT BUILDING (B). |
| | FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |