Plan Review Notes
Plan Review Notes For Permit 20030565
Permit Number 20030565
Review Stop M
Sequence Number 2
Notes
Date Text
2020-08-04 15:51:012ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20030565
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE 1ST CYCLE REVIEW COMMENTS 12,13,14 AND
 MAKE SURE THIS HAS BEEN COMPLETED. PLEASE UPLOAD THE
 CORRECT DOCUMENTS FOR BUILDING B ONLY; ELEVATOR MACHINE
 ROOM LOAD CALS STILL SHOW BIKE ROOM AND BUILDING A;
 UNIT 1A1 LOAD CALCS V2 IN PROJECT INFORMATION (NOTES)
 STILL SHOWS BUILDING A-UNIT 1A 1ST FLOOR. UNIT 1A2 LOAD
 CALCS V2 SHEET 3 UNDER PROJECT INFORMATION (NOTES)
 PLEASE SHOW THE CORRECT BUILDING (B).UNIT 2A1 EWN LOAD
 CALCS- PLEASE IDENTIFY WHICH BUILDING. PLEASE RECHECK
 ALL LOAD CALCULATION SHEETS AND ENERGY CALCULATION
 SHEETS TO VERIFY THEY HAVE THE CORRECT BUILDING (B).
 FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  