Plan Review Notes
Plan Review Notes For Permit 20030565
Permit Number 20030565
Review Stop M
Sequence Number 1
Notes
Date Text
2020-04-08 16:47:161ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030565
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE VENTILATION CALCULATIONS FOR ENTIRE
 BUILDING. ARE YOU USING FBC M 402 FOR NATURAL
 VENTILATION OR 403 FOR MECHANICAL?
 2) PLEASE SHOW HOW THE MECHANICAL ROOM IN EACH LIVING
 SPACE MEETS SECTION 602 OF THE FBC M FOR PLENUMS.
 3) PLEASE PROVIDE A DETAIL DRAWING OF THE DRYER AND
 DRYER DUCT CONNECTION IN THE AHU CLOSET. THE DRYER DUCT
 APPEARS TO STOP IN THE CEILING. FBC FS 107.2.1
 4) PLEASE SHOW CFM?S FOR ALL RETURN GRILLES AND
 TRANSFER GRILLES. FBC M 601.5(3)
 5) PLEASE SHOW RETURN PATH BACK TO THE AHU. ARE THE
 DOUBLE DOORS LOUVERED? IF SO THEN PLEASE PROVIDE DETAIL
 AND SHEET NUMBER. FBC FS 107.2.1
 6) PLEASE SHOW EACH KITCHEN WILL COMPLY WITH FBC M
 TABLE 403.3.2.3.
 7) PLEASE SHOW THE EXHAUST TERMINATIONS MEET SECTION
 501.3(3) OF THE FBC M.
 8) PLEASE SHOW THE INTAKE OPENING LOCATIONS MEET
 SECTION 401.4 OF THE FBC M.
 9) PLEASE IDENTIFY ALL LOAD CALCULATIONS AS YOU DID IN
 ?UNIT 2B1 LOAD CALCS? UNDER PROJECT INFORMATION, THIS
 IDENTIFIES THE BUILDING OR BUILDINGS WHERE THIS UNIT IS
 LOCATED.
 10) DOCUMENTS UPLOADED TITLED ? ELEVATOR MACHINE ROOM
 LOAD CALCS.PDF? ARE FOR ? BUILDING A-BIKE ROOM?. PLEASE
 UPLOAD THE CORRECT DOCUMENT FOR THIS BUILDING B
 ELEVATOR MACHINE ROOM LOAD CALCS.PDF.
 11) DOCUMENTS UPLOADED TITLED ?INIT 1A1 LOAD
 CALCULATIONS PDF? ARE FOR BUILDING A. PLEASE UPLOAD
 LOAD CALCULATIONS FOR THE CORRECT BUILDING (B).
 12) PLEASE IDENTIFY BUILDING B ON ALL OF THE ENERGY
 CALCULATIONS.
 13) PLEASE IDENTIFY EACH LOAD CALCULATION AS TO THE
 BUILDING IT IS LOCATED IN. EITHER BUILDING A OR
 BUILDING B.
 14) DOCUMENTS UPLOADED TITLED ?UNIT 1A2 LOAD CALCS.PDF?
 ARE FOR BUILDING A. PLEASE UPLOAD CALCULATIONS FOR
 BUILDING B.
 15) UNDER ?MECHANICAL VENTILATION? IN THE ENERGY
 CALCULATIONS PLEASE SHOW BATHROOM AND KITCHEN EXHAUST
 CFM. IT APPEARS THE CFM?S SHOWN ARE ONLY FOR THE
 BATHROOMS. FBC FS 107.2.1; FBC M TABLE 403.3.2.2
 16) SHEET M-4.1: PLEASE SHOW ROOF ACCESS. FBC M 306.5
 17) SHEET M-4.1: PLEASE SHOW EQUIPMENT ON THE ROOF
 MEETS FBC M 304.11 (GUARDS)
 18) SHEET M-5.3: THE RETURN AIR TRANSFER FOR THE
 BEDROOM IS NOT INSIDE THE ROOM. PLEASE SHOW THIS RETURN
 AIR TRANSFER IN THE CORRECT LOCATION. FBC FS 107.2.1
 19) SHEET M-5.4: PLEASE SHOW THE REQUIRED DAMPERS IN
 ALL PENETRATIONS OF THE 2 HR RATED WALL AT THE
 ELECTRICAL ROOM.
 20) SHEET M-5.4: PLEASE PROVIDE A DETAIL DRAWING OF THE
 AHU ROOM SHOWING THE AHU?S, THE RETURN AIR DUCT AND HOW
 IT RETURNS TO THE AHU AND THE O/A DUCT AND LOCATION IT
 ENTERS THE AHU?S. FBC FS 107.2.1
 21) . FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF
 CERTIFY DIGITAL SIGATURES AND SEALS PER FBC FS 668.003.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  