| 2020-10-07 06:47:33 | 1) SUBMIT FIRE STOPPING DETAILS FOR NON-METALLIC PIPE |
| | THROUGH FIRE RATE FLOORS.A DETAIL HAS BEN SUBMITTED FOR |
| | WALLS BUT NOT FOR FLOORS AS PREIOUSLY REQUESTED.WPB |
| | AMEND. TO FBC SEC. 107.3.5.1.1 (4). |
| | 2) SHT.P7.4 - UNIT 2A - #1208 - RISER 2SA2 IS LABELED |
| | AS 2S2A ON SHTS.P2.1 & P5.2. CLARIFY. 2ND REQUEST. |
| | 3) SHT. P7.4 - UNIT 2A - #1208 THE WATER CLOSET AND THE |
| | TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING |
| | SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A |
| | SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED. |
| | FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 4) SHT. P7.4 - UNIT 1A - #1207 - THE SHOWER AND WATER |
| | CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE |
| | THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT |
| | IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 5) SHT. P7.4 - UNIT 1A - #1207 - THE WATER CLOSET AND |
| | THE TUB ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A |
| | SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED. |
| | FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 6) SHT. P7.4 - UNIT 1A - #1206 - THE WATER CLOSET AND |
| | THE TUB ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A |
| | SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED. |
| | FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 7) SHT. P7.4 - UNIT 2B - #1205 - THE SHOWER AND WATER |
| | CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE |
| | THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT |
| | IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 8) SHT. P7.4 - UNIT 2B - #1205 - THE WATER CLOSET AND |
| | THE TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING |
| | SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A |
| | SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED. |
| | FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 9) SHT. P7..4 - UNIT 2B - #1204 - THE WATER CLOSET AND |
| | THE TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING |
| | SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A |
| | SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED. |
| | FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 10) SHT. P7.5 - UNIT2B - #1204 - THE SHOWER AND WATER |
| | CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE |
| | THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT |
| | IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 11) SHT. P7.5 - UNIT 1A - #1203 - THE WATER CLOSET AND |
| | THE TUB ARE NOT VENTED. FBC-PLUMBING SEC.901.2, |
| | 901.2.1,SINCE THESE FIXTURES ARE ON A SEPARATE FIXTURE |
| | BRANCH, A VENT IS RQUIRED. FBC-PLUMBING SEC.901.2, |
| | 901.2.1, |
| | 12) SHT. P7.5 - UNIT 1A - #1202 - THE WATER CLOSET AND |
| | THE TUB ARE NOT VENTED. FBC-PLUMBING SEC.901.2, |
| | 901.2.1,SINCE THESE FIXTURES ARE ON A SEPARATE FIXTURE |
| | BRANCH, A VENT IS RQUIRED. FBC-PLUMBING SEC.901.2, |
| | 901.2.1, |
| | 13) SHT. P7.5 - UNIT 2A - #1201 - THE TUB AND WATER |
| | CLOSET IN THE HALL BATHROOM ARE NOT VENTED.SINCE THESE |
| | FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT IS |
| | REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1. |
| | 14) SHT. P7.5 - UNIT 2A - #1201 - THE SHOWER AND WATER |
| | CLOSET IN THE MASTER BATH ARE NOT VENTED. THE LAVATORY |
| | FIXTURE BRANCH SHALL BE LOCATED BETWEEN THE WATER |
| | CLOSET AND THE SHOWER.FBC-PLUMBING SEC.901.2, 912.1. |
| | 15) SHT. P7.6 - RISER S1A - THE TUB AND WATER CLOSET |
| | ARE NOT VENTED. THE LAVATORY DRAIN AND VENT SHALL BE |
| | LOCATED BETWEEN THE WATER CLOSET AND THE SHOWER. |
| | FBC-PLUMBING SEC.901.2, 912.1. |
| | 16) SHT. P7.7 - UNIT 2A - RISER S2A - THE TUB AND WATER |
| | CLOSET ARE NOT VENTED.THE LAVATORY DRAIN AND VENT SHALL |
| | BE LOCATED BETWEEN THE WATER CLOSET AND THE TUB. |
| | FBC-PLUMBING SEC.901.2, 912.1. |
| | 17) SHT. P7.7 - UNIT 2A - RISER 2S2A - THE SHOWER AND |
| | WATER CLOSET ARE NOT VENTED. THE LAVATORY DRAIN AND |
| | VENT SHALL BE LOCATED BETWEEN THE WATER CLOSET AND THE |
| | SHOWER. FBC-PLUMBING SEC.901.2, 912.1. |
| | 18) SHT. P7.8 - UNIT 2B - RISER S2B - AS DRAWN, THE |
| | WATER CLOSET AND TUB ARE NOT VENTED.THE LAVATORY DRAIN |
| | AND VENT SHALL BE LOCATED BETWEEN THE WATER CLOSET AND |
| | THE TUB OR THE WATER CLOSET AND TUB SHALL BE INSTALLED |
| | ON A HORIZONTAL WET VENT. FBC-PLUMBING SEC.901.2, |
| | 912.1. |
| | 19) SHT. P7.8 - UNIT 2B - RISER S2B - THE WATER CLOSET |
| | AND THE SHOWER ARE NOT VENTED. SINCE THESE FIXTURES ARE |
| | ON A SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED. |
| | FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 20) SHT. P7.8 - UNIT 1B - RISER S1B - THE WATER CLOSET |
| | AND THE SHOWER ARE NOT VENTED. SINCE THESE FIXTURES ARE |
| | ON A SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED. |
| | FBC-PLUMBING SEC.901.2, 901.2.1, |
| | 21) SHT. P7.2 - DETAIL #1 - THE WATER CLOSET AND SHOWER |
| | ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A SEPARATE |
| | FIXTURE BRANCH, A VENT IS REQUIRED. FBC-PLUMBING |
| | SEC.901.2, 901.2.1, |
| | 22) SHT. P7.2 - DETAIL #3 - THE DISHWASHER SHALL |
| | DISCHARGE INDIRECTLY IN ACCORDANCE WITH FBC-PLUMBING |
| | SEC.802.1.6. |
| | |
| | REVIEW IS INCOMPLETE |