Plan Review Notes
Plan Review Notes For Permit 20030563
Permit Number 20030563
Review Stop P
Sequence Number 3
Notes
Date Text
2020-10-07 06:47:331) SUBMIT FIRE STOPPING DETAILS FOR NON-METALLIC PIPE
 THROUGH FIRE RATE FLOORS.A DETAIL HAS BEN SUBMITTED FOR
 WALLS BUT NOT FOR FLOORS AS PREIOUSLY REQUESTED.WPB
 AMEND. TO FBC SEC. 107.3.5.1.1 (4).
 2) SHT.P7.4 - UNIT 2A - #1208 - RISER 2SA2 IS LABELED
 AS 2S2A ON SHTS.P2.1 & P5.2. CLARIFY. 2ND REQUEST.
 3) SHT. P7.4 - UNIT 2A - #1208 THE WATER CLOSET AND THE
 TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING
 SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A
 SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED.
 FBC-PLUMBING SEC.901.2, 901.2.1,
 4) SHT. P7.4 - UNIT 1A - #1207 - THE SHOWER AND WATER
 CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE
 THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT
 IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1,
 5) SHT. P7.4 - UNIT 1A - #1207 - THE WATER CLOSET AND
 THE TUB ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A
 SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED.
 FBC-PLUMBING SEC.901.2, 901.2.1,
 6) SHT. P7.4 - UNIT 1A - #1206 - THE WATER CLOSET AND
 THE TUB ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A
 SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED.
 FBC-PLUMBING SEC.901.2, 901.2.1,
 7) SHT. P7.4 - UNIT 2B - #1205 - THE SHOWER AND WATER
 CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE
 THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT
 IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1,
 8) SHT. P7.4 - UNIT 2B - #1205 - THE WATER CLOSET AND
 THE TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING
 SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A
 SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED.
 FBC-PLUMBING SEC.901.2, 901.2.1,
 9) SHT. P7..4 - UNIT 2B - #1204 - THE WATER CLOSET AND
 THE TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING
 SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A
 SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED.
 FBC-PLUMBING SEC.901.2, 901.2.1,
 10) SHT. P7.5 - UNIT2B - #1204 - THE SHOWER AND WATER
 CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE
 THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT
 IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1,
 11) SHT. P7.5 - UNIT 1A - #1203 - THE WATER CLOSET AND
 THE TUB ARE NOT VENTED. FBC-PLUMBING SEC.901.2,
 901.2.1,SINCE THESE FIXTURES ARE ON A SEPARATE FIXTURE
 BRANCH, A VENT IS RQUIRED. FBC-PLUMBING SEC.901.2,
 901.2.1,
 12) SHT. P7.5 - UNIT 1A - #1202 - THE WATER CLOSET AND
 THE TUB ARE NOT VENTED. FBC-PLUMBING SEC.901.2,
 901.2.1,SINCE THESE FIXTURES ARE ON A SEPARATE FIXTURE
 BRANCH, A VENT IS RQUIRED. FBC-PLUMBING SEC.901.2,
 901.2.1,
 13) SHT. P7.5 - UNIT 2A - #1201 - THE TUB AND WATER
 CLOSET IN THE HALL BATHROOM ARE NOT VENTED.SINCE THESE
 FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT IS
 REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1.
 14) SHT. P7.5 - UNIT 2A - #1201 - THE SHOWER AND WATER
 CLOSET IN THE MASTER BATH ARE NOT VENTED. THE LAVATORY
 FIXTURE BRANCH SHALL BE LOCATED BETWEEN THE WATER
 CLOSET AND THE SHOWER.FBC-PLUMBING SEC.901.2, 912.1.
 15) SHT. P7.6 - RISER S1A - THE TUB AND WATER CLOSET
 ARE NOT VENTED. THE LAVATORY DRAIN AND VENT SHALL BE
 LOCATED BETWEEN THE WATER CLOSET AND THE SHOWER.
 FBC-PLUMBING SEC.901.2, 912.1.
 16) SHT. P7.7 - UNIT 2A - RISER S2A - THE TUB AND WATER
 CLOSET ARE NOT VENTED.THE LAVATORY DRAIN AND VENT SHALL
 BE LOCATED BETWEEN THE WATER CLOSET AND THE TUB.
 FBC-PLUMBING SEC.901.2, 912.1.
 17) SHT. P7.7 - UNIT 2A - RISER 2S2A - THE SHOWER AND
 WATER CLOSET ARE NOT VENTED. THE LAVATORY DRAIN AND
 VENT SHALL BE LOCATED BETWEEN THE WATER CLOSET AND THE
 SHOWER. FBC-PLUMBING SEC.901.2, 912.1.
 18) SHT. P7.8 - UNIT 2B - RISER S2B - AS DRAWN, THE
 WATER CLOSET AND TUB ARE NOT VENTED.THE LAVATORY DRAIN
 AND VENT SHALL BE LOCATED BETWEEN THE WATER CLOSET AND
 THE TUB OR THE WATER CLOSET AND TUB SHALL BE INSTALLED
 ON A HORIZONTAL WET VENT. FBC-PLUMBING SEC.901.2,
 912.1.
 19) SHT. P7.8 - UNIT 2B - RISER S2B - THE WATER CLOSET
 AND THE SHOWER ARE NOT VENTED. SINCE THESE FIXTURES ARE
 ON A SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED.
 FBC-PLUMBING SEC.901.2, 901.2.1,
 20) SHT. P7.8 - UNIT 1B - RISER S1B - THE WATER CLOSET
 AND THE SHOWER ARE NOT VENTED. SINCE THESE FIXTURES ARE
 ON A SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED.
 FBC-PLUMBING SEC.901.2, 901.2.1,
 21) SHT. P7.2 - DETAIL #1 - THE WATER CLOSET AND SHOWER
 ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A SEPARATE
 FIXTURE BRANCH, A VENT IS REQUIRED. FBC-PLUMBING
 SEC.901.2, 901.2.1,
 22) SHT. P7.2 - DETAIL #3 - THE DISHWASHER SHALL
 DISCHARGE INDIRECTLY IN ACCORDANCE WITH FBC-PLUMBING
 SEC.802.1.6.
  
 REVIEW IS INCOMPLETE