Plan Review Notes
Plan Review Notes For Permit 20030563
Permit Number 20030563
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-10 05:43:031) SHT.A-0.1 - DETAIL #3 - UNIT 2A - THIS LAYOUT DOES
 NOT COMPLY WITH THE FAIR HOUSING ACT DESIGN MANUAL,
 CHAPTER 7, PAGE 7.56 & 7.57. THE ONLY FIXTURE PERMITTED
 TO BE ADJACENT TO THE SHOWER IS A LAVATORY MOUNTED ON
 THE CONTROL WALL BESIDE THE SHOWER AND MAY OVERLAP THE
 CLEAR FLOOR SPACE BY A MAXIMUM OF 6 INCHES. THE PORTION
 OF THE LAVATORY THAT OVERLAPS THE CLEAR FLOOR SPACE
 MUST HAVE KNEE SPACE BELOW OR A REMOVABLE VANITY
 CABINET. A 30 INCH WIDE BY 48 INCH DEEP CLEAR FLOOR
 SPACE MUST BE PROVIDED PARALLEL TO THE SHOWER AND FLUSH
 WITH THE CONTROL WALL. 2ND REQUEST.
 2) THE PRESSURE CYLINDER FOR THE ELEVATOR SHALL BE
 PROTECTED IN ACCORDANCE WITH 2017 FBC-BUILDING
 SEC.3011. I COULD NOT FIND THIS DETAIL ON THE PLANS.
 PLEASE SUBMIT THE SPECIFIC PAGE WHERE THIS DETAIL CAN
 BE FOUND. 2ND REQUEST.
 3) FIRESTOPPING DETAILS HAVE BEEN SUBMITTED FOR METAL
 PIPE THROUGH RATED WALLS AND FLOORS. IF PVC PIPE IS TO
 BE INSTALLED, SUBMIT FIRESTOPPING ASSEMBLY DETAILS FOR
 THE PVC PIPE THROUGH RATED FLOORS AND WALLS.WPB AMEND.
 TO FBC SEC. 107.2.1, 107.3.5.1.1.
 4) SHT. P7.2 - DETAIL #1 - A MAXIMUM OF 10 FIXTURE
 UNITS SHALL BE VENTED BY A 1 1/2 INCH VENT PER
 FBC-PLUMBING TABLE 906.1.AS DRAWN, 15 FIXTURE UNITS ARE
 BEING VENTED BY THE 1 1/2 INCH VENT. REFER TO
 FBC-PLUMBING TABLE 709.1 FOR FIXTURE UNIT VALUE FOR A
 BATHROOM GROUP.
 5) SHT. P7.3 - THE HOSE BIBBS SHALL BE EQUIPPED WITH
 SEPARATE SHUTOFF VALVES PER FBC-PLUMBING SEC.606.2 (2).
 6) SHT. P7.3 - PROVIDE RISER TAGS FOR THE 1 1/2 INCH
 LINE UP TO THE 2ND & 3RD FLOOR UNITS AND FOR THE 4 INCH
 SANITARY FROM THE 2ND & 3RD FLOOR UNITS. WPB AMEND. TO
 FBC SEC. 107.3.5.1.3.
 7) SHT. P7.4 - UNIT 2A - #1208 - RISER 2SA2 APPEARS TO
 BE LABELED AS 2S2A ON SHT. P5.2.. CLARIFY.
 8) SHT. P7.4 - UNIT 2A - #1208 - RISER 2V2A APPEARS TO
 BE LABELED AS 2V2D ON SHT. P2.1. CLARIFY.
 9) SHT.P7.4 - UNIT 1A - #'S 1206 & 1207 - FIRST FLOOR
 SANITARY - THE KITCHEN SINK IS DISCHARGING INTO THE
 HORIZONTAL WET VENT. ONLY FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE WET VENTED HORIZONTAL BRANCH
 DRAIN. THE KITCHEN SINK SHALL CONNECT TO THE 4 INCH
 HORIZONTAL DRAIN DOWNSTREAM OF THE SHOWER.FBC-PLUMBING
 SEC.912.1.
 10) SHT. P7.4 - UNIT 2B - #1205 - FIRST FLOOR SANITARY
 - THE SHOWER AND WATER CLOSET ARE NOT VENTED.THE
 LAVATORY DRAIN & VENT SHALL BE LOCATED BETWEEN THE
 WATER CLOSET AND THE SHOWER. FBC PLUMBING SEC. 901.2,
 11) SHT. P7.4 - THE 2 INCH SANITARY LINE FOR THE PET
 WASH GOES NOWHERE. SHOW THE CONTINUATION AND
 TERMINATION POINT OF THIS LINE AND IDENTIFY IT WITH A
 RISER TAG IF APPLICABLE. WPB AMEND. TO FBC SEC.
 107.2.1.
 12) SHT. P7.4 - VENT RISER V1B SHOWN AT THE PET WASH IS
 NOT SHOWN ON SHT. P2.1 - CLARIFY.
 13) SHT. P7.4 - UNIT 2B - #1204 - MASTER BATH - VENT
 VTB APPEARS TO BE LABELED AS 2V2B ON SHT. P2.1.
 CLARIFY.
 14) SHT. P7.4 - UNIT 2B - #1205 - HALL BATH - RISER
 2V2B APPEARS TO BE LABELED AS V2B ON SHT. P2.1.THIS
 ALSO OCCURS ON THE 2ND AND 3RD FLOOR PLAN ON P2.1.
 CLARIFY.
 15) SHT. P7.5 - UNIT 2B -#1204 - HALL BATH - RISER 2V2B
 APPEARS TO BE LABELED AS V2B ON SHT. P2.1. THIS ALSO
 OCCURS ON THE 2ND AND 3RD FLOOR PLAN ON P2.1. CLARIFY.
 16) SHT. P7.5 - UNIT 2B - #1204 - RISER S2B IS NOT
 SHOWN ON SHT. P2.1 - CLARIFY.
 17) SHT. P7.5 - UNIT 2B -#1204 - HALL BATH - FIRST
 FLOOR SANITARY - THE SHOWER AND WATER CLOSET ARE NOT
 VENTED.THE LAVATORY DRAIN & VENT SHALL BE LOCATED
 BETWEEN THE WATER CLOSET AND THE SHOWER. FBC PLUMBING
 SEC. 901.2,
 18) SHT. P7.5 - UNIT 2A -#1201 - MASTER BATH - RISER
 LABELED AS V2A APPEARS TO BE LABELED AS 2V2D ON SHT.
 P2.1. CLARIFY.
 19) SHT. P7.5 - UNIT 2A - #1201 -MASTER BATH - RISER
 LABELED AS S2A APPEARS TO BE LABELED AS 2S2A ON SHT.
 P2.1. THIS ALSO OCCURS ON THE 2ND & 3RD FLOORS. ALSO,
 THE VENT RISER FOR MASTER BATH LAVATORY IS NOT SHOWN ON
 THE PLAN VIEW FOR THE 2ND AND 3RD FLOORS. CLARIFY
 20) SHT. P7.5 - UNIT 2A - #1201 - HALL BATH - THE
 SHOWER AND WATER CLOSET ARE NOT VENTED.THE LAVATORY
 DRAIN & VENT SHALL BE LOCATED BETWEEN THE WATER CLOSET
 AND THE SHOWER. FBC PLUMBING SEC. 901.2,
 21) SHT. P7.5 - UNIT 2A - #1201 - HALL BATH - RISER
 LABELED AS 2V2A APPEARS TO BE LABELED AS V2A ON SHT
 P2.1. THIS ALSO OCCURS ON THE 2ND AND 3RD FLOORS.
 CLARIFY.
 22) SHT. P7.5 - UNIT 2A - #1201 - RISER LABELED AS 2S2A
 APPEARS TO BE LABELED AS S2A ON SHT. P2.1. THIS ALSO
 OCCURS IN THE SAME UNIT ON THE 2ND & 3RD FLOORS.
 CLARIFY.
 23) SHT. P7.6 - RISER S1A - THE SHOWER AND WATER CLOSET
 ARE NOT VENTED.THE LAVATORY DRAIN & VENT SHALL BE
 LOCATED BETWEEN THE WATER CLOSET AND THE SHOWER. FBC
 PLUMBING SEC. 901.2,
 24) SHT. P7.7 - UNIT 2A - RISER S2A - THE SHOWER AND
 WATER CLOSET ARE NOT VENTED.THE LAVATORY DRAIN & VENT
 SHALL BE LOCATED BETWEEN THE WATER CLOSET AND THE
 SHOWER. FBC PLUMBING SEC. 901.2.
 25) SHT. P7.7 - UNIT 2A - RISER 2SA2 FOR THE MASTER
 BATH APPEARS TO BE LABELED AS 2S2A ON SHT. P5.2 -
 CLARIFY.
 26) CHECK ALL THE RISER TAGS ON THE PLAN VIEW SHEETS
 AGAINST THE SANITARY RISER DIAGRAMS TO ENSURE THE RISER
 TAGS CORRELATE THROUGH EACH FLOOR. REFER TO SHEETS
 P2.1, P7.4, P7.5, P7.6 & P7.7. WPB AMEND. TO FBC SEC.
 107.2.1.
 27) SHT. P7.8 - UNIT 2B - RISER S2B - 2ND & 3RD FLOOR -
 THE SHOWER AND WATER CLOSET IN THE HALL BATH ARE NOT
 VENTED.THE LAVATORY DRAIN & VENT SHALL BE LOCATED
 BETWEEN THE WATER CLOSET AND THE SHOWER. FBC PLUMBING
 SEC. 901.2,
 28) SHT. P7.8 - UNIT 2B - RISER S2B - THE KITCHEN SINK
 IS DISCHARGING INTO THE HORIZONTAL WET VENT. ONLY
 FIXTURES WITHIN THE BATHROOM GROUP SHALL CONNECT TO THE
 WET VENTED HORIZONTAL BRANCH DRAIN. THE KITCHEN SINK
 SHALL CONNECT TO THE 4 INCH HORIZONTAL DRAIN DOWNSTREAM
 OF THE SHOWER.FBC-PLUMBING SEC.912.1.
 29) SHT.P7.8 - DETAIL #1 - RISERS 2V2B & V2B - A
 MAXIMUM OF 10 FIXTURE UNITS SHALL BE VENTED BY A 1 1/2
 INCH VENT PER FBC-PLUMBING TABLE 906.1.AS DRAWN, 15
 FIXTURE UNITS ARE BEING VENTED BY THE 1 1/2 INCH VENT.
 REFER TO FBC-PLUMBING TABLE 709.1 FOR FIXTURE UNIT
 VALUE FOR A BATHROOM GROUP.
 30) PLEASE IDENTIFY THE TUBS AS TUBS ON THE RISER
 DIAGRAMS AND NOT AS SHOWERS.
 31) SUBMIT A CONDENSATE RISER FOR REVIEW. SIZING SHALL
 COMPLY WITH FBC-PLUMBING SEC.314.
 32) THE SANITARY RISERS SHOW THE DIRECTION OF FLOW AT
 SEVERAL AREAS OF THE RISERS. REVISE THE RISERS TO
 REFLECT CORRECT DIRECTION OF FLOW.
 33) SUBMIT A WATER HEATER PAN DRAIN RISER FOR
 REVIEW.WPB AMEND. TO FBC SEC. 107.2.1.
 34) IF A SUMP PUMP WILL BE INSTALLED IN THE ELEVATOR
 SUMP, THE INSTALLATION SHALL COMPLY WITH FBC-PLUMBING
 SEC.1003.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW