Plan Review Notes
Plan Review Notes For Permit 20030563
Permit Number 20030563
Review Stop M
Sequence Number 2
Notes
Date Text
2020-08-04 12:14:072ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20030563
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-6.2 (NOTE-2) INDICATES THE USE OF A DRYER
 BOOSTER FAN, PLEASE PROVIDE THE SPECS FOR THIS DEVICE
 ALONG WITH THE UL APPROVAL. FBC FS 107.2.1
  
 2) SHEET M-5.3 INDICATES A MFCU-1A FOR THE PET WASHING
 ROOM AND A MFCU-1B FOR THE BICYCLE STORAGE ROOM. SHEET
 M-7.1 DOES NOT HAVE THESE UNITS LISTED IN THE EQUIPMENT
 SCHEDULE. PLEASE BE CONSISTENT ON BOTH SHEETS. FBC FS
 107.2.1
  
 3) SHEET M-5.3 AND SHEET M-7.1 DO NOT SHOW OUTSIDE AIR
 PROVIDED FOR THE OCCUPIABLE PET WASH ROOM OR THE
 BICYCLE STORAGE ROOM, PLEASE SHOW VENTILATION
 CALCULATIONS FOR THESE AREAS ALONG WITH HOW OUTSIDE AIR
 WILL BE BROUGHT INTO THESE AREAS. FBC M 401.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  