| Date |
Text |
| 2020-08-04 12:14:07 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20030563 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-6.2 (NOTE-2) INDICATES THE USE OF A DRYER |
| | BOOSTER FAN, PLEASE PROVIDE THE SPECS FOR THIS DEVICE |
| | ALONG WITH THE UL APPROVAL. FBC FS 107.2.1 |
| | |
| | 2) SHEET M-5.3 INDICATES A MFCU-1A FOR THE PET WASHING |
| | ROOM AND A MFCU-1B FOR THE BICYCLE STORAGE ROOM. SHEET |
| | M-7.1 DOES NOT HAVE THESE UNITS LISTED IN THE EQUIPMENT |
| | SCHEDULE. PLEASE BE CONSISTENT ON BOTH SHEETS. FBC FS |
| | 107.2.1 |
| | |
| | 3) SHEET M-5.3 AND SHEET M-7.1 DO NOT SHOW OUTSIDE AIR |
| | PROVIDED FOR THE OCCUPIABLE PET WASH ROOM OR THE |
| | BICYCLE STORAGE ROOM, PLEASE SHOW VENTILATION |
| | CALCULATIONS FOR THESE AREAS ALONG WITH HOW OUTSIDE AIR |
| | WILL BE BROUGHT INTO THESE AREAS. FBC M 401.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |