| 2020-08-13 13:33:16 | NEW 3 STORY APT. BLDG. |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 2ND REVIEW |
| | 1) PRODUCT APPROVAL PROVIDED FOR THE DWELLING UNIT |
| | INSWING EXTERIOR DOORS DOES NOT MEET THE WATER |
| | INFILTRATION REQUIREMENTS OF FBC 1709.5.1 |
| | 2) DOORS THAT OPEN INTO THE UNITS NEED TO COMPLY WITH |
| | WATER INFILTRATION REQUIREMENTS PER FBC 1709.5.1 |
| | 3) PRODUCT APPROVAL 19-0219.11 FOR THE SLIDING GLASS |
| | DOOR DOES NOT MEET THE IMPACT REQUIREMENTS FBC 1609.1.2 |
| | (PLEASE PROVIDE A COMPLETE SHUTTER PRODUCT APPROVAL.) |
| | 4) PRODUCT APPROVAL 17-0614.05 FOR THE FIXED GLASS DOES |
| | NOT MEET THE IMPACT REQUIREMENTS FBC 1609.1.2 (PLEASE |
| | PROVIDE A COMPLETE SHUTTER PRODUCT APPROVAL) |
| | 5) PLEASE SHOW THE FLOORING SOUND TRANSMISSION TO |
| | COMPLY WITH FBC 1207 AS NOTED BELOW (A, B AND C) (YOU |
| | NEED TO PROVIDE THE ACOUSTICAL LAB TEST REPORTS) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NONCOMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |