Plan Review Notes
Plan Review Notes For Permit 20030563
Permit Number 20030563
Review Stop B
Sequence Number 2
Notes
Date Text
2020-08-13 13:33:16NEW 3 STORY APT. BLDG.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 2ND REVIEW
 1) PRODUCT APPROVAL PROVIDED FOR THE DWELLING UNIT
 INSWING EXTERIOR DOORS DOES NOT MEET THE WATER
 INFILTRATION REQUIREMENTS OF FBC 1709.5.1
 2) DOORS THAT OPEN INTO THE UNITS NEED TO COMPLY WITH
 WATER INFILTRATION REQUIREMENTS PER FBC 1709.5.1
 3) PRODUCT APPROVAL 19-0219.11 FOR THE SLIDING GLASS
 DOOR DOES NOT MEET THE IMPACT REQUIREMENTS FBC 1609.1.2
 (PLEASE PROVIDE A COMPLETE SHUTTER PRODUCT APPROVAL.)
 4) PRODUCT APPROVAL 17-0614.05 FOR THE FIXED GLASS DOES
 NOT MEET THE IMPACT REQUIREMENTS FBC 1609.1.2 (PLEASE
 PROVIDE A COMPLETE SHUTTER PRODUCT APPROVAL)
 5) PLEASE SHOW THE FLOORING SOUND TRANSMISSION TO
 COMPLY WITH FBC 1207 AS NOTED BELOW (A, B AND C) (YOU
 NEED TO PROVIDE THE ACOUSTICAL LAB TEST REPORTS)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NONCOMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  