| 2020-04-04 11:47:32 | PLUMBING: |
| | 1) SHT. A-0.1 - DETAILS #1, #2 & #3 - SHOWS THE |
| | CENTERLINE OF THE WATER CLOSET FROM THE EDGE OF THE TUB |
| | AND/OR SHOWER AS ONE- FOOT SEVEN INCHES, ONE- FOOT NINE |
| | INCHES AND ONE- FOOT EIGHT INCHES RESPECTIVELY. THE |
| | DISTANCE SHALL BE 0NE -FOOT SIX INCHES ( 18" ) ABSOLUTE |
| | AS REQUIRED BY THE FAIR HOUSING ACT DESIGN MANUAL, |
| | CHAPTER 6, PG. 6.7. THESE DIMENSIONS MUST ALSO BE |
| | CHANGED ON THE ELEVATION DRAWINGS. |
| | 2) SHT. A-0.1 - DETAIL #7 - SHOW THE WIDTH OF THE |
| | PROPOSED REINFORCEMENT FOR THE TUB. THE LENGTH IS SHOWN |
| | AS 48 INCHES.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHT. A-0.1 - THE UNITS THAT HAVE A SHOWER DO NOT |
| | COMPLY WITH THE REQUIREMNT FOR THE CLEAR FLOOR SPACE |
| | THAT IS REQUIRED BY THE FHA DESIGN MANUAL CHAPTER 7, |
| | PG.7.56. AS PROPOSED, THIS LAYOUT DOES NOT COMPLY WITH |
| | HAVING THE WATER CLOSET NEXT TO THE SHOWER.A 30 INCH |
| | WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE MUST BE PROVIDED |
| | AT SHOWER STALLS, PARALLEL TO THE FIXTURE AND FLUSH |
| | WITH THE CONTROL WALL. FHA DESIGN MANUAL PART TWO, |
| | CHAPTER 7, PART B, PG. 7.56.. |
| | 4) SHT. A-0.1 - DETAIL #3 NOTES "SEE DETAIL #6 FOR GRAB |
| | BAR REINFORCEMENT AT SHOWER." DETAIL #6 SHOWS |
| | REINFORCEMENT AT TOILETS.REVISE THE NOTE TO REFER TO |
| | DETAIL #8. |
| | 5) SHT. A-0.1 - DETAIL #3 NOTES " SEE DETAIL #8 FOR |
| | REINFORCEMENT AT TOILET." DETAIL #8 SHOWS REINFORCEMENT |
| | AT SHOWERS. REVISE THE NOTE TO REFER TO DETAIL #6. |
| | 6) SHT. A-0.1 - DETAIL #8 - THE SHOWER REINFORCEMENT |
| | THAT IS SHOWN FOR A FUTURE SHOWER SEAT DOES NOT COMPLY |
| | WITH THE FAIR HOUSING ACT DESIGN MANUAL. THE |
| | REINFORCING MUST START AT THE FLOOR AND RISE TO A |
| | MINIMUM HEIGHT OF 24 INCHES, NOT START 6 INCHES ABOVE |
| | THE FLOOR PER PART TWO, CHAPTER 6, PG. 6.13 OF THE FAIR |
| | HOUSING ACT DESIGN MANUA. REVISE THE DETAIL. |
| | 7) THE PLANS REFER TO A GYM. I DID NOT SEE A GYM |
| | LOCATED ON THE PLANS. CLARIFY. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 8) SHT. A-1.3 - DETAIL #5 - CLARIFY THE CLEARANCES FOR |
| | THE WATER CLOSET FROM THE EDGE OF THE VANITY AND THE |
| | TUB/SHOWER. COMPLY WITH FHA DESIGN MANUAL. |
| | 9) SHT. A-1.4 - INTERIOR ELEVATION #6 - THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 18 INCHES PER THE FHA |
| | DESIGN MANUAL.. THE PLANS SHOWS ONE FOOT NINE INCHES |
| | (21 INCHES). |
| | 10) SHT.A-1.5 - INTERIOR ELEVATIONS #5 & #9 - THE |
| | CENTERLINE TO THE WATER CLOSET SHALL BE 18 INCHES TO |
| | THE CENTERLINE, NOT 20 INCHES AS SHOWN.FHA DESIGN |
| | MANUAL, PART TWO, CHAPTER 7, PART B PG. 7.43. |
| | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PET |
| | WASH UNIT. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 12) SUBMIT ADDITIONAL INFORMATION ON THE RAINWATER |
| | CALCULATIONS. SHOW HOW YOU ARRIVED AT THE FINAL |
| | RESULTS. THE PARAPET WALL MUST BE INCLUDED IN THE |
| | RAINWATER CALCULATIONS PER THE 2017 FBC-PLUMBING |
| | SECS.1106.4, 1106.5.SEE SHT. A-3. |
| | 13) IS THE ELEVATOR A TRACTION TYPE OR HYDRAULIC TYPE? |
| | IF OF A HYDRAULIC TYPE , THE PRESSURE CYLINDER SHALL BE |
| | PROTECTED IN ACCORDANCE WITH 2017 FBC -BUILDING |
| | SEC.3011. |
| | 14) THE PLANS SHOW A BBQ GRILL. SUBMIT DETAILS ON THE |
| | GRILL AND ANY VENTILATION REQUIREMENTS. IS THIS A GAS |
| | GRILL OR A CHARCOAL BURNING GRILL. CLARIFY ON THE |
| | PLANS. |
| | 15) SUBMIT GAS RISER DIAGRAM AND MANUFACTURER'S |
| | SPECIFICATIONS FOR THE GRILL IF IT UTILIZES GAS.WPB |
| | AMEND. TO FBC SEC. 107.3.5.1.6. |
| | 16) SUBMIT FIRESTOPPING DETAILS FOR PIPE PENETRATIONS |
| | THROUGH FRAMED RATED WALLS. THE SUBMITTED DETAIL IS FOR |
| | PENETRATIONS THROUGH A CONCRETE FLOOR OR A BOLCK WALL. |
| | WPB AMEND. TO FBC SEC. 107.3.5.1.1. |
| | 17) SHT. P-1.0 - IDENTIFY ALL RISERS ON THE PLUMBING |
| | SHEETS.. PROVIDE RISER TAG NUMBERS FOR EACH RISER ( |
| | WATER & SANITARY).WPB AMEND. TO FBC SEC.107.3.5.1.3. |
| | 18) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER |
| | DIAGRAM SHOWING ALL SANITARY RISERS AND PROVIDE RISER |
| | TAG NUMBERS SO THE RISERS WILL CORRELATE WITH RISERS |
| | THAR ARE TO BE SHOWN ON THE FLOOR PLAN. WPB AMEND. TO |
| | FBC SEC. 107.3.5.1.3. |
| | 19) SHT. P-2.1 - THE FIRST FLOOR PLAN SHOWS TRENCH |
| | DRAINS BY THE ELEVATORS.AND THE PLAN REFERS TO THE |
| | CIVIL DRAWINGS. THESE DRAINS ARE NOT SHOWN ON THE CIVIL |
| | DRAWINGS. CLEARLY SHOW THE LOCATION OF THESE DRAINS ON |
| | THE PLANS AND SPECIFY THE SPECIFIC SHEET WHERE THEY ARE |
| | LOCATED. WPB AMEND. TO FBC SEC. 107.1, 107.3.5.1.3. |
| | 20) SHT. P-2.1 - THERE ARE NO PIPE SIZES ON THE PIPES |
| | AND THE RISERS NEED TO HAVE RISER TAGS AND IDENTIFIED |
| | AS TO THE USE. WPB AMEND. TO FBC SEC. 107.2.1.REFER TO |
| | THE SPECIFIC CIVIL DRAWING WHERE THE REQUIRED |
| | INFORMATION CAN BE FOUND. |
| | 21) THE UNITS WITH THE HALL BATH HAVE THE HALL BATH |
| | MISSING FROM THE SANITARY AND WATER RISER. WPB AMEND. |
| | TO FBC SEC. 107.3.5.1.3. |
| | 22) SHTS. P-5.1 & P-5.2 - KEYNOTE #2 IS NOT SHOWN ON |
| | THE PLANS. CLARIFY. |
| | 23) SHT. P-7.1 - A FULL OPEN VALVE IS REQUIRED AT THE |
| | BASE OF THE WATER RISER PER 2017 FBC-PLUMBING SEC.606.1 |
| | (4). |
| | 24) SUBMIT A COMPLETE WATER RISER FOR THE 2 BATH UNIT. |
| | WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 25) SHT. P-7.2 - DETAIL #3 - THE KITCHEN SINKS ARE NOT |
| | VENTED. 2017 FBC-PLUMBING SECS.901.2,901.2.1. |
| | 26) SHT. P-7.3 - DETAIL #1 - THE FLOOR DRAINS ARE NOT |
| | VENTED. 2017 FBC-PLUMBING SEC.901.2,901.2.1. |
| | 27) A TRAP AND VENT IS REQUIRED ON THE PET WASH |
| | DRAIN.2017 FBC-PLUMBING SEC. 1002.1, SECS.901.2,901.2.1 |
| | 28) THE PLUMBING SHEETS NOTE" SEE PLANS FOR |
| | CONTINUATION" OF PLUMBING LINES. LIST THE SPECIFIC |
| | SHEET WHERE THESE CONTINUATION LINES CAN BE FOUND. WPB |
| | AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 29) A SEPARATE SHUTOFF VALE IS REQUIRED ON THE WATER |
| | SUPPLY TO THE PET RINSE AREA. 2017 FBC-PLUMBING |
| | SEC.606.2 (1) (3). |
| | 30) SHT. P-7.3 - IDENTIFY THE LOCATION OF THE TWO FLOOR |
| | DRAINS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 31) SHT. P-8.1 - PLUMBING FIXTURE CONNECTION SCHEDULE - |
| | NOTE #3 STATES " FIXTURES SHALL BE IN COMPLIANCE WITH |
| | MIAMI-DADE COUNTY WATER USE EFFICIENCY STANDARDS. |
| | CLARIFY. |
| | 32) SHT. P-8.1 - PIPE MATERIAL SCHEDULE - NOTE #6 |
| | REFERS TO THE 2007 FLORIDA PLUMING CODE. THE CODE THAT |
| | IS IN EFFECT IS THE 2017 EDITION. REVISE THE NOTE. |
| | 33) SEPARATE PEMITS WILL BE REQUIRED FOR ALL BACKFLOW |
| | PREVENTION DEVICES. |
| | 34) SUBMIT IRRIGATION PLANS IF A NEW IRRIGATION SYSTEM |
| | IS GOING TO BE INSTALLED. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 35) SHT. P-1.0 - KEYED NOTE #3 REFERS TO THE CIVIL |
| | DRAWINGS FOR THE CONTINUATION OF THE DRAIN LINE FROM |
| | THE ROOF. THESE LINES ARE NOT SHOWN ON CIVIL DRAWING |
| | C-2.1. CLARIFY. |
| | 36) THE WATER VALVES FOR THE STACKED WASHER SHALL BE |
| | PROVIDED WITH ACCESS IN ACCORDANCE WITH 2017 |
| | FBC-PLUMBING SEC.606.3. |
| | |
| | FIRE PROTECTION: |
| | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| | SPRINKLER HEADS TO BE INSTALLED IN THE LIGHT HAZARD AND |
| | ORDINARY HAZARD AREAS. NFPA 13R SEC. 8.1.7 (12). |
| | 2) SHT. FP-1 REFERS TO FP-1 FOR THE POINT OF SERVICE. |
| | THE POINT OF SERVICE IS NOT SHOWN ON FP-1. CLARIFY.SHOW |
| | THE POINT OF SERVICE ON SHT. C-2.3 PER FL. STATUTE |
| | 633.021. |
| | 3) THERE IS NO SPRINKLER HEAD SHOWN IN THE ELEVATOR |
| | PIT. COMPLY WITH NFPA 13 SEC. 8.15.5. |
| | 4) SUBMIT A KEYNOTE LEGEND FOR THE KEYNOTES ON SHT. |
| | FP-1, BUILDING A RISER DIAGRAM. |
| | 5) SHT. FP-1 - BUILDING A RISER DIAGRAM SHOWS THE BASE |
| | OF THE RISER TAG AS BEING ON THE THIRD FLOOR. CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |